5.1 Basic Concept of Redundant System
5.1.4 System Consistency Check
5
REDUNDANT SYSTEM FUNCTIONS
(6) Parameter Valid Drive Settings Consistency Check
(a) Check points
The control system and standby system parameter valid drive settings (dip switch
SW2,SW3) are checked.
(b) Inconsistency Errors
Table5.18 displays the consistency errors that occurred when the parameter valid
drive settings are inconsistent.
If the "FILE DIFF." occurs in the standby CPU module, Use the dip switches SW2,
SW3 of the control system and standby system CPU modules so that the settings
will be consistent.
* 1: If a stop error occurs in the standby CPU module, the following continuation error will occur in the
control system CPU module: "STANDBY SYS. DOWN (error code: 6300)".
Diagram 5.16 Parameter Valid Drive Settings Consistency Check
Table5.18 Parameter Valid Drive Settings Inconsistency Errors
Execution Conditions
Error Description
• When both systems are powered ON
simultaneously
• When both system CPU modules are
unreset (RESET/L.CLR switch is set to the
neutral position) simultaneously
The following stop error occurs in the control system
and standby system CPU modules: "FILE DIFF.
(error code: 6001)".
• When one system starts up after the other
• When the separate mode is changed to the
backup mode
• When reconnecting the tracking cable
The following stop error occurs in the standby system
CPU module only: "FILE DIFF. (error code: 6001)".
*1
Control
system
Standby
system
Tracking cable
1
2
4
3
5
1
2
4
3
5
An error occurs because the dip switch (SW3) setting is incorrect