5
- 47
5.3 The System Switching Function
5.3.3 System Switching Execution Possibility
5
Table5.30 Operations When System Switching Cannot Be Executed Due to Tracking Cable Disconnection
System
Switching
Method
Control System
Switching Condition
Before System Switching
System Status After
System Switching
Condition
Operation After Tracking Cable
Disconnection
System A
System B
System A
System B
Automatic
System
Switching
Stop Error Other Than
Watchdog Timer Errors
Control
System
Standby
System
Control
System
Standby
System
System switching will not be executed.
Watchdog Timer Error
Control
System
Standby
System
Standby
System
Standby
System
System switching will not be executed.
Hardware Failure
Control
System
Standby
System
Control
System
Standby
System
System switching will not be executed.
Power OFF
Control
System
Standby
System
Control
System
Standby
System
System switching will not be executed.
Reseting
Control
System
Standby
System
Control
System
Standby
System
System switching will not be executed.
System Switching
Request by Network
Module
Control
System
Standby
System
Control
System
Standby
System
System switching will not be executed.
Manual
System
Switching
System Switching
Using GX Developer
Control
System
Standby
System
Control
System
Standby
System
System switching will not be executed.
System Switching by
System Switching
Instruction
Control
System
Standby
System
Control
System
Standby
System
System switching will not be executed.
Table5.31 When System Switching Cannot Be Executed Due to Network Error of Standby System
System
Switching
Method
Control System
Switching Condition
System Status Before
System Switching
System Status After
System Switching
Condition
Operation After B System Power
OFF
ON
System A
System B
System A
System B
Automatic
System
Switching
Stop Error Other Than
Watchdog Timer Error
Control
System
Standby
System
Standby
System
Control
System
Startup as control system
Watchdog Timer Error
Control
System
Standby
System
Standby
System
Standby
System
Startup as control system
Hardware Failure
Control
System
Standby
System
Standby
System
Control
System
Startup as control system
Power OFF
Control
System
Standby
System
Standby
System
Control
System
Startup as control system
Reseting
Control
System
Standby
System
Standby
System
Control
System
Startup as control system
System Switching
Request by Network
Module
Control
System
Standby
System
Control
System
Standby
System
Startup as standby system
Manual
System
Switching
System Switching
Using GX Developer
Control
System
Standby
System
Control
System
Standby
System
Startup as standby system
System Switching by
System Switching
Instruction
Control
System
Standby
System
Control
System
Standby
System
Startup as standby system