2) Confirmation by GX Developer
Whether memory copy is normally completed or abnormally completed can be
checked on the "Redundant operation" screen of GX Developer.
(2) Memory Copy from Control System to Standby System Using GX
Developer
The following provides the procedure for executing memory copy function using GX
Developer and the relevant operations.
(a) Procedure
1) Connect the control system and standby system CPU modules with a tracking
cable and power on the standby system.
* 2: If the standby system CPU module is replaced and the parameters are not stored in the new CPU
module, the "MISSING PARA. (error code: 2200)" stop error will occur.
2) Connect GX Developer to the control system CPU module.
Identify the control system CPU module on the "CONTROL" LED or with the
special relay (SM1515 (Control Status): ON, SM1516 (Standby status): OFF).
Diagram 5.77 Redundant Operation Screen Showing
Normal Completion
Diagram 5.78 Redundant Operation Screen Showing
Abnormal Completion
Diagram 5.79 LED Indications When Tracking Cable Is Connected
Q12PRHCPU
MODE
RUN
ERR.
USER
BAT.
BOOT
BACKUP
CONTROL
SYSTEM A
SYSTEM B
Q12PRHCPU
MODE
RUN
ERR.
USER
BAT.
BOOT
BACKUP
CONTROL
SYSTEM A
SYSTEM B
Control system CPU module
Standby system CPU module
ON (red)
ON (red)
Flashing (red)*
2
ON (red)