8
- 51
8.3 Replacing Module in Redundant System
8.3.9 Tracking Cable Replacement
8
(2) Replacement Procedure
The procedure of replacing the tracking cable is shown in the Diagram 8.36.
POINT
Make sure to replace the tracking cable after powering off the standby system (or
setting the RESET/L.CLR switch to the RESET position (reset).
If the tracking cable is connected or disconnected while both systems are running,
it may result in either of the followings.
• The scan time is extended and the "WDT ERROR (ERROR CODE: 5000,
5001) occurs.
• The "TRK.CIR.ERROR (ERROR CODE: 1112, 1113, 1116)" occurs and
the redundant CPU operation stops.
Power OFF the Standby System
Power off the standby system. (Or, set the RESET/L.CLR switch to the RESET position (reset).
Tacking Cable Replacement
(1) Disconnect the tracking cable from the control system CPU module.
Refer to Section 3.3, for disconnecting the tracking cable.
(2) Disconnect the tracking cable from the standby system CPU module.
(3) Connect the tracking cable connector to the standby system CPU module.
Refer to Section 3.3, for disconnecting the tracking cable.
(4) Connect the tracking cable connector to the control system CPU module.
Power ON the Standby System
(1) Confirm that the RUN/STOP switch of the standby system CPU module is in the same
position as that of the control system CPU module.
(2) Power on the control system.(OR Set the RESET/L.CLR switch of the standby system CPU
module to the central position (reset switch neutral position).
Confirm the Power Supply Module's POWER LED
Confirm that the power supply module POWER LED is lit (green), and that power is being supplied
properly.
Diagram 8.36 Tracking Cable Replacement
Start
Start standby system