8.1 Troubleshooting Flow
8.1.6 When System Switching has failed
8
TROUBLESHOOTING
NO
Wait for online program change to
complete.
YES
NO
Wait for the memory copy from control
system to standby system to complete.
Confirm individual information
(SD16) for control system errors.
YES
Depending on the control system error
code, confirm below and resolve the fault.
NO
YES
Specify a value other than 0 for
SP.CONTSW.Turn ON
SM1592.For separate mode
operation, Change the program to
respond to SP.CONTSW
instructions not from the standby
system but from the control
system.
3)
4)
4)
4)
2)
Has an operation error
occurred from the control
system's system switching
instruction?
Is SD16=8?
Is SD16=9?
4100 :
4120 :
4121 :
NO
YES
Change the tracking cable.
Is SD16=1?