5.10 Redundant CPU Functions Restricted in Redundant System
5.10.1 Enforced ON/OFF of external I/O
5
5.10 Redundant CPU Functions Restricted in Redundant System
This section explains the following Redundant CPU functions that are restricted in a
redundant system.
• Enforced ON/OFF of external I/O
• Remote operation
Refer to the following manual for details of each function.
QCPU User's Manual (Function Explanation/Program Fundamentals)
5.10.1 Enforced ON/OFF of external I/O
The Redundant CPU can forcibly turn ON/OFF the enforced ON/OFF of external I/O
operation from GX Developer.
The registered ON/OFF information can be cleared by GX Developer operation.
(1) CPU modules that can be forcibly turned ON/OFF
The enforced ON/OFF of the external I/O can be executed for only the control system
CPU module. (It cannot be executed for the standby system CPU.)
If registration/change/clear of the forced I/O ON/OFF status is made to the standby
system CPU, the error dialog box (in Diagram 5.96) will appear on GX Developer.
In this case, change the connection target of GX Developer to the "control system".
Diagram 5.96 Error Dialog Box That Appears When Forced ON/OFF/Cancel Is Executed in Standby System