14 TROUBLESHOOTING
14.5 List of Error Codes
611
14
1B03H
Home position return
speed error
The setting value of the home position return basic
parameter "[Pr.46] Home position return speed" is
outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Correct the setting value and turn the PLC READY
signal [Y0] from OFF to ON.
1B04H
Home position return
speed error
The setting value of the home position return basic
parameter "[Pr.46] Home position return speed"
exceeds the "[Pr.8] Speed limit value".
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
After the setting value is equal to or less than the
"[Pr.8] Speed limit value", turn the PLC READY signal
[Y0] from OFF to ON.
1B05H
Home position return
speed error
The setting value of the home position return basic
parameter "[Pr.46] Home position return speed" is
smaller than "[Pr.7] Bias speed at start".
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
After the setting value is set to equal to or more than
"[Pr.7] Bias speed at start", turn the PLC READY signal
[Y0] from OFF to ON.
1B06H
Creep speed error
The setting value of the home position return basic
parameter "[Pr.47] Creep speed" is outside the setting
range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
Correct the setting value and turn the PLC READY
signal [Y0] from OFF to ON.
1B07H
Creep speed error
The setting value of the home position return basic
parameter "[Pr.47] Creep speed" is larger than the
"[Pr.46] Home position return speed".
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
After the setting value is set to equal to or less than the
"[Pr.46] Home position return speed", turn the PLC
READY signal [Y0] from OFF to ON.
1B08H
Creep speed error
The setting value of the home position return basic
parameter "[Pr.47] Creep speed" is smaller than the
"[Pr.7] Bias speed at start".
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
After the setting value is set to equal to or more than
the "[Pr.7] Bias speed at start", turn the PLC READY
signal [Y0] from OFF to ON.
1B09H
Home position return
retry error
The setting value of the home position return basic
parameter "Home position return retry" is outside the
setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1B0AH
Setting for the
movement amount
after near-point dog
ON error
The setting value of the home position return detailed
parameter "Setting for the movement amount after
near-point dog ON" is outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1B0BH
Home position return
acceleration time
selection error
The setting value of the home position return detailed
parameter "Home position return acceleration time
selection" is outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1B0CH
Home position return
deceleration time
selection error
The setting value of the home position return detailed
parameter "Home position return deceleration time
selection" is outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1B0DH
Home position return
torque limit value
error
The setting value of the home position return detailed
parameter "Home position return torque limit value" is
outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1B0EH
Home position return
torque limit value
error
The home position return detailed parameter "Home
position return torque limit value" has exceeded the
detailed parameter 1 "Torque limit setting value".
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1B10H
Speed designation
during home position
shift error
The setting value of the home position return detailed
parameter "Speed designation during home position
shift" is outside the setting range.
[Operation status at error occurrence]
The READY signal [X0] is not turned ON.
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
Error code
(Hexadecimal)
Error name
Error details and causes
Remedy
Содержание RD77MS16
Страница 1: ...MELSEC iQ R Simple Motion Module User s Manual Application RD77MS2 RD77MS4 RD77MS8 RD77MS16 ...
Страница 2: ......
Страница 316: ...314 9 COMMON FUNCTIONS 9 4 External Input Signal Select Function Program example ...
Страница 317: ...9 COMMON FUNCTIONS 9 4 External Input Signal Select Function 315 9 ...
Страница 574: ...572 13 PROGRAMMING 13 4 Positioning Program Examples Parameter initialization program Flash ROM write program ...
Страница 575: ...13 PROGRAMMING 13 4 Positioning Program Examples 573 13 Error reset program Axis stop program ...
Страница 643: ......