4 HIGH-LEVEL POSITIONING CONTROL
4.3 Setting the Block Start Data
Block start
In a "block start (normal start)", the positioning data groups of a block are continuously executed in a set PLC starting from the
positioning data set in "[Da.12] Start data No." by one start.
The control examples are shown when the "block start data" and "positioning data" are set as shown in the setting examples.
Setting examples
■
Block start data setting example
■
Positioning data setting example
*1
"1 block" is defined as all the data continuing from the positioning data in which "continuous positioning control" or "continuous path
control" is set in the "[Da.1] Operation pattern" to the positioning data in which "independent positioning control (Positioning complete)"
is set.
Axis 1 block start data
[Da.11] Shape
[Da.12] Start data No.
[Da.13] Special start
instruction
[Da.14] Parameter
1st point
1: Continue
1
0: Block start
2nd point
1: Continue
2
0: Block start
3rd point
1: Continue
5
0: Block start
4th point
1: Continue
10
0: Block start
5th point
0: End
15
0: Block start
Axis 1 positioning data
No.
[Da.1] Operation pattern
1
00: Positioning complete
2
11: Continuous path control
1 block
3
01: Continuous positioning
control
4
00: Positioning complete
5
11: Continuous path control
1 block
6
00: Positioning complete
10
00: Positioning complete
15
00: Positioning complete
Содержание RD77MS16
Страница 1: ...MELSEC iQ R Simple Motion Module User s Manual Application RD77MS2 RD77MS4 RD77MS8 RD77MS16 ...
Страница 2: ......
Страница 316: ...314 9 COMMON FUNCTIONS 9 4 External Input Signal Select Function Program example ...
Страница 317: ...9 COMMON FUNCTIONS 9 4 External Input Signal Select Function 315 9 ...
Страница 574: ...572 13 PROGRAMMING 13 4 Positioning Program Examples Parameter initialization program Flash ROM write program ...
Страница 575: ...13 PROGRAMMING 13 4 Positioning Program Examples 573 13 Error reset program Axis stop program ...
Страница 643: ......