324
9 COMMON FUNCTIONS
9.7 Virtual Servo Amplifier Function
Restrictions
• The following monitor data of virtual servo amplifier differ from the actual servo amplifier.
n: Axis No. - 1
• The operation for external signal selection function of virtual servo amplifier differs from the actual servo amplifier.
• The following monitor data of virtual servo amplifier differ from the actual servo amplifiers. The writing operation is possible
in the virtual servo amplifier.
n: Axis No. - 1
Storage item
Storage details
Buffer memory address
[Md.102]
Deviation counter value
Always "0".
2452+100n
2453+100n
[Md.105]
Connected device
As the following connected devices artificially.
• When "1: SSCNET
/H" is set in "[Pr.97] SSCNET setting"
00001000H: MR-J4-_B
• When "0: SSCNET
" is set in "[Pr.97] SSCNET setting"
00000100H: MR-J3-_B
58660
58661
[Md.106]
Servo amplifier software No.
Always "0".
2464+100n
to
2469+100n
[Md.107]
Parameter error No.
Always "0".
2470+100n
[Md.108]
Servo status1
• READY ON (b0), Servo ON (b1): Changed depending on the all
axis servo ON signal [Y1] and "[Cd.100] Servo OFF command"
• Control mode (b2, b3): Indicates control mode.
• Servo alarm (b7): Always OFF
• In-position (b12): Always ON
• Torque limit (b13): Changed depending on "[Md.104] Motor
current value". (Refer to the 2nd and 3rd bullets of restrictions for
details.)
• Absolute position lost (b14): Always OFF
• Servo warning (b15): Always OFF
2477+100n
[Md.109]
Regenerative load ratio/Optional data
monitor output 1
Always "0".
2478+100n
[Md.110]
Effective load torque/Optional data
monitor output 2
Always "0".
2479+100n
[Md.111]
Peak torque ratio/Optional data monitor
output 3
Always "0".
2480+100n
[Md.112]
Optional data monitor output 4
Always "0".
2481+100n
[Md.119]
Servo status2
• Zero point pass (b0): Always ON
• Zero speed (b3): Changed depending on the command speed
• Speed limit (b4): Always ON when the value other than "0" is set
to the command torque at torque control mode. Otherwise,
always OFF.
• PID control (b8): Always OFF
2476+100n
Function
Operation
External signal selection function
When "1: Servo amplifier" is set in "[Pr.116] FLS signal selection", "[Pr.117] RLS signal selection", and "[Pr.118] DOG
signal selection", the external signal status immediately after the power supply ON is shown below.
• Upper/lower limit signal (FLS, RLS): ON
• Near-point dog signal (DOG): OFF
Change the signal status in "[Md.30] External input signal". (Refer to the 3rd bullet of restrictions for details.)
Torque limit function
Turns ON/OFF torque limit ("[Md.108] Servo status1": b13) depending on "[Md.104] Motor current value". (Refer to the
3rd bullet of restrictions for details.)
Storage item
Storage details
Buffer memory address
[Md.30]
External input signal
When "1: Servo amplifier" is set in "[Pr.116] FLS signal selection", "[Pr.117] RLS signal
selection", and "[Pr.118] DOG signal selection", the external input signal status can be
operated by turning ON/OFF the following signals.
• b0: Lower limit signal
• b1: Upper limit signal
• b6: Near-point dog signal
2416+100n
[Md.104]
Motor current value
"0" is set after immediately power supply ON.
The motor current value can be emulated by changing this monitor data in user side.
2456+100n
Содержание RD77MS16
Страница 1: ...MELSEC iQ R Simple Motion Module User s Manual Application RD77MS2 RD77MS4 RD77MS8 RD77MS16 ...
Страница 2: ......
Страница 316: ...314 9 COMMON FUNCTIONS 9 4 External Input Signal Select Function Program example ...
Страница 317: ...9 COMMON FUNCTIONS 9 4 External Input Signal Select Function 315 9 ...
Страница 574: ...572 13 PROGRAMMING 13 4 Positioning Program Examples Parameter initialization program Flash ROM write program ...
Страница 575: ...13 PROGRAMMING 13 4 Positioning Program Examples 573 13 Error reset program Axis stop program ...
Страница 643: ......