14 TROUBLESHOOTING
14.5 List of Error Codes
609
14
1AC1H
Stop group 1 sudden
stop selection error
The setting value of the detailed parameter 2 "Stop
group 1 sudden stop selection" is outside the setting
range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1AC2H
Stop group 2 sudden
stop selection error
The setting value of the detailed parameter 2 "Stop
group 2 sudden stop selection" is outside the setting
range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1AC3H
Stop group 3 sudden
stop selection error
The setting value of the detailed parameter 2 "Stop
group 3 sudden stop selection" is outside the setting
range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1AC4H
Outside allowance
circular interpolation
error width
The setting value of the detailed parameter 2
"Allowance circular interpolation error width" is outside
the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1AC5H
External command
function selection
error
The setting value of the detailed parameter 2 "External
command function selection" is outside the setting
range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from
OFF to ON: The READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/sudden stop) of the detailed
parameter 2 sudden stop selection (stop group 3). (Note
that the deceleration stop only occurs during the
manual pulse generator operation.)
With the setting brought into the setting range, turn the
PLC READY signal [Y0] from OFF to ON.
1AC6H
Manual pulse
generator speed limit
mode error
The setting value of the detailed parameter 2 "[Pr.122]
Manual pulse generator speed limit mode" is outside
the setting range.
[Operation status at error occurrence]
At the power on or when the PLC READY signal [Y0] is
turned from OFF to ON: The READY signal [X0] is not
turned ON.
At start: The system does not operate.
Correct the setting value and turn the PLC READY
signal [Y0] from OFF to ON.
Error code
(Hexadecimal)
Error name
Error details and causes
Remedy
Содержание RD77MS16
Страница 1: ...MELSEC iQ R Simple Motion Module User s Manual Application RD77MS2 RD77MS4 RD77MS8 RD77MS16 ...
Страница 2: ......
Страница 316: ...314 9 COMMON FUNCTIONS 9 4 External Input Signal Select Function Program example ...
Страница 317: ...9 COMMON FUNCTIONS 9 4 External Input Signal Select Function 315 9 ...
Страница 574: ...572 13 PROGRAMMING 13 4 Positioning Program Examples Parameter initialization program Flash ROM write program ...
Страница 575: ...13 PROGRAMMING 13 4 Positioning Program Examples 573 13 Error reset program Axis stop program ...
Страница 643: ......