14 - 31
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.7 Leakage current breaker
(1) Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a
commercial power supply.
Select a leakage current breaker according to the following formula, and ground the servo amplifier,
servo motor, etc. securely.
Make the input and output cables as short as possible, and also make the grounding cable as long as
possible (about 30cm (11.8 in)) to minimize leakage currents.
Rated sensitivity current 10 {Ig1 Ign Iga K (Ig2 Igm)} [mA] ..........(14.2)
K: Constant considering the harmonic contents
Leakage current breaker
Type
Mitsubishi
products
K
Models provided with
harmonic and surge
reduction techniques
NV-SP
NV-SW
NV-CP
NV-CW
NV-L
1
SM
Servo
amplifier
Noise
filter
NV
Ig1 Ign
Iga
Ig2
Igm
Cable
Cable
General models
BV-C1
NFB
NV-L
3
Ig1:
Leakage current on the electric channel from the leakage current breaker to the input terminals
of the servo amplifier (Found from Fig. 14.1.)
Ig2:
Leakage current on the electric channel from the output terminals of the servo amplifier to the
servo motor (Found from Fig. 14.1.)
Ign:
Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF)
Iga:
Leakage current of the servo amplifier (Found from Table 14.6.)
Igm:
Leakage current of the servo motor (Found from Table 14.5.)
Table 14.5 Servo Motor's Leakage
Current Example (Igm)
Table 14.6 Servo Amplifier's Leakage
Current Example (Iga)
Servo Motor
Output [kW]
Leakage
Current [mA]
Servo Amplifier
Capacity [kW]
Leakage
Current [mA]
0.05 to 0.5
0.1
0.6 to 1.0
0.1
0.1 to 0.6
0.1
1.2 to 2.2
0.2
3 to 3.5
0.3
0.7 to 3.5
0.15
Table 14.7 Leakage Circuit Breaker
Selection Example
Servo Amplifier
Rated Sensitivity
Current of Leakage
Circuit Breaker
120
100
80
60
40
20
0
2 3.5
5.5
8 1422 38 80 150
30 60 100
Fig. 14.1 Leakage Current Example
(Ig1, Ig2) for CV Cable Run
in Metal Conduit
Cable size[mm
2
]
[mA]
Le
ak
ag
e
cu
rr
en
t
MR-J2-10C
to
MR-J2-350C
15 [mA]
Downloaded from
Содержание MELSERVO MR-J2 C Series
Страница 11: ...A 10 MEMO Downloaded from ManualsNet com search engine ...
Страница 33: ...1 16 1 FUNCTIONS AND CONFIGURATION MEMO Downloaded from ManualsNet com search engine ...
Страница 73: ...3 36 3 SIGNALS AND WIRING MEMO Downloaded from ManualsNet com search engine ...
Страница 127: ...5 18 5 PARAMETERS MEMO Downloaded from ManualsNet com search engine ...
Страница 145: ...6 18 6 SERVO CONFIGURATION SOFTWARE MEMO Downloaded from ManualsNet com search engine ...
Страница 155: ...7 10 7 DISPLAY AND OPERATION MEMO Downloaded from ManualsNet com search engine ...
Страница 189: ...8 34 8 COMMUNICATION FUNCTIONS MEMO Downloaded from ManualsNet com search engine ...
Страница 201: ...10 2 10 INSPECTION MEMO Downloaded from ManualsNet com search engine ...
Страница 211: ...11 10 11 TROUBLESHOOTING MEMO Downloaded from ManualsNet com search engine ...
Страница 219: ...12 8 12 SPECIFICATIONS MEMO Downloaded from ManualsNet com search engine ...
Страница 227: ...13 8 13 CHARACTERISTICS MEMO Downloaded from ManualsNet com search engine ...