4 - 4
4. OPERATION
(f) Home position return
Perform home position return as required. Refer to Section 4.4 for home position return types. A
parameter setting example for dog type home position return is given here.
Parameter
Name
Setting
Description
No.8
Home position return type
000
Dog type home position return is selected.
Home position return is started in address
incremented direction.
Proximity dog (DOG) is valid when DOG-
SG are opened.
No.9
Home position return speed
1000
Motion is made up to proximity dog at 1000r/min.
No.10
Creep speed
10
Motion is made up to home position at 10r/min.
No.11
Home position shift distance
0
No home position shift
No.42
Home position return position data
Set the current position at home position return
completion.
No.43
Moving distance after proximity dog
Not used in dog type home position return.
After setting the above parameters, switch power off once. Then switch power on again to make the
set parameter values valid.
Set the input signals as listed below and switch on the forward rotation start (ST1) to execute
home position return.
Device Name
Symbol
ON/OFF
Description
Automatic/manual selection
MD0
ON
Point table No. selection 1
DI0
OFF
Point table No. selection 2
DI1
OFF
Home position return mode is selected.
Servo-on
SON
ON
Servo is switched on.
(g) Automatic operation
Set the input signals as listed below and switch on the forward rotation start (ST1) to execute
automatic operation in accordance with point table No.1.
Device Name
Symbol
ON/OFF
Description
Automatic/manual selection
MD0
ON
Automatic operation mode is selected.
Servo-on
SON
ON
Servo is switched on.
Forward rotation stroke end
LSP
ON
Forward rotation side limit switch is turned on.
Reverse rotation stroke end
LSN
ON
Reverse rotation side limit switch is turned on.
Point table No. selection 1
DI0
ON
Point table No. selection 2
DI1
OFF
Point table No.1 is selected.
(h) Stop
In any of the following statuses, the servo amplifier interrupts and stops the operation of the servo
motor.
When the servo motor used is equipped with an electromagnetic brake, refer to Section 3.9 (3).
Note that forward rotation stroke end (LSP), reverse rotation stroke end (LSN) off has the same
stopping pattern as described below.
1) Servo-on (SON) OFF
The base circuit is shut off and the servo motor coasts.
2) Alarm occurrence
When an alarm occurs, the base circuit is shut off and the dynamic brake is operated to bring the
servo motor to a sudden stop.
3) Forced stop (EMG) OFF
The base circuit is shut off and the dynamic brake is operated to bring the servo motor to a
sudden stop. Servo forced warning (A.E6) occurs.
4) Forward rotation stroke end (LSP), reverse rotation stroke end (LSN) OFF
The droop pulse value is erased and the servo motor is stopped and servo-locked. It can be run in
the opposite direction.
Downloaded from
Содержание MELSERVO MR-J2 C Series
Страница 11: ...A 10 MEMO Downloaded from ManualsNet com search engine ...
Страница 33: ...1 16 1 FUNCTIONS AND CONFIGURATION MEMO Downloaded from ManualsNet com search engine ...
Страница 73: ...3 36 3 SIGNALS AND WIRING MEMO Downloaded from ManualsNet com search engine ...
Страница 127: ...5 18 5 PARAMETERS MEMO Downloaded from ManualsNet com search engine ...
Страница 145: ...6 18 6 SERVO CONFIGURATION SOFTWARE MEMO Downloaded from ManualsNet com search engine ...
Страница 155: ...7 10 7 DISPLAY AND OPERATION MEMO Downloaded from ManualsNet com search engine ...
Страница 189: ...8 34 8 COMMUNICATION FUNCTIONS MEMO Downloaded from ManualsNet com search engine ...
Страница 201: ...10 2 10 INSPECTION MEMO Downloaded from ManualsNet com search engine ...
Страница 211: ...11 10 11 TROUBLESHOOTING MEMO Downloaded from ManualsNet com search engine ...
Страница 219: ...12 8 12 SPECIFICATIONS MEMO Downloaded from ManualsNet com search engine ...
Страница 227: ...13 8 13 CHARACTERISTICS MEMO Downloaded from ManualsNet com search engine ...