14 - 32
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions:
SM
Servo
amplifier
MR-J2-60C
HA-FF63
2mm
2
5m(196.85inch)
Ig1
Ig2
Iga
Igm
NV
2mm
2
5m(196.85inch)
Use a leakage current breaker designed for suppressing harmonics/surges.
Find the terms of Equation (14.2) from the diagram:
Ig1 20
1000
5
0.1 [mA]
Ig2 20
1000
5
0.1 [mA]
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (14.2):
Ig 10 {0.1 0 0.1 1 (0.1 0.1)}
4 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity
current (Ig) of 4[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/CP/SW/CW/HW series.
Downloaded from
Содержание MELSERVO MR-J2 C Series
Страница 11: ...A 10 MEMO Downloaded from ManualsNet com search engine ...
Страница 33: ...1 16 1 FUNCTIONS AND CONFIGURATION MEMO Downloaded from ManualsNet com search engine ...
Страница 73: ...3 36 3 SIGNALS AND WIRING MEMO Downloaded from ManualsNet com search engine ...
Страница 127: ...5 18 5 PARAMETERS MEMO Downloaded from ManualsNet com search engine ...
Страница 145: ...6 18 6 SERVO CONFIGURATION SOFTWARE MEMO Downloaded from ManualsNet com search engine ...
Страница 155: ...7 10 7 DISPLAY AND OPERATION MEMO Downloaded from ManualsNet com search engine ...
Страница 189: ...8 34 8 COMMUNICATION FUNCTIONS MEMO Downloaded from ManualsNet com search engine ...
Страница 201: ...10 2 10 INSPECTION MEMO Downloaded from ManualsNet com search engine ...
Страница 211: ...11 10 11 TROUBLESHOOTING MEMO Downloaded from ManualsNet com search engine ...
Страница 219: ...12 8 12 SPECIFICATIONS MEMO Downloaded from ManualsNet com search engine ...
Страница 227: ...13 8 13 CHARACTERISTICS MEMO Downloaded from ManualsNet com search engine ...