202
Selection of operation mode and operation location
(11) Switching of operation mode by external signals (X65, X66 signals)
When
Pr. 79
= any of "0, 2, 6", the operation mode switching signals (X65, X66) can be used to change the PU or External
operation mode to the Network operation mode during a stop (during a motor stop or start command OFF). (
Pr. 79
= "6"
Switch-over mode can be changed during operation)
When switching between the Network operation mode and PU operation mode
1)Set
Pr. 79
to "0" (initial value) or "6".
2)Set
"10" in
Pr. 340 Communication startup mode selection
.
3)Set "65" in any of
Pr. 178 to Pr. 184
to assign the NET-PU operation switching signal (X65) to the terminal.
4)The operation mode changes to the PU operation mode when the X65 signal turns ON, or to the Network operation
mode when the X65 signal turns OFF.
When switching between the Network operation mode and External operation mode
1) Set
Pr. 79
to "0 (initial value), 2, 6 or 7". (At the
Pr. 79
setting of "7", the operation mode can be switched when the X12
(MRS) signal turns ON.)
2) Set "0 (initial value) or 1" in
Pr. 340 Communication startup mode selection
.
3) Set "66" in any of
Pr. 178 to Pr. 184
to assign the NET-PU operation switching signal (X66) to the terminal.
4) The operation mode changes to the Network operation mode when the X66 signal turns ON, or to the External
operation mode when the X66 signal turns OFF.
Pr. 340
Setting
Pr. 79
Setting
X65 Signal State
Remarks
ON (PU)
OFF (NET)
10
0
(initial value)
PU operation mode
∗1
NET operation mode
1
PU operation mode
Fixed to PU operation mode
2
NET operation mode
Fixed to NET operation mode
3, 4
External/PU combined operation mode
External/PU combined mode fixed
6
PU operation mode
∗1
NET operation mode
Operation mode can be switched with operation continued
7
X12 (MRS)
ON
Switching among the External and
PU operation mode is enabled
Output stop in External operation mode
X12 (MRS)
OFF
External operation mode
Forcibly switched to External operation mode
∗1
NET operation mode when the X66 signal is ON.
∗2
PU operation mode is selected when the X16 signal is OFF. PU operation mode also when
Pr. 550 NET mode operation command source selection
= "0"
(communication option command source) and the communication option is not fitted.
External operation mode when the X16 signal is ON.
Pr. 340
Setting
Pr. 79
Setting
X66 Signal State
Remarks
ON (NET)
OFF (External)
0
(initial
value), 1
0
(initial value)
NET operation mode
External operation
mode
1
PU operation mode
Fixed to PU operation mode
2
NET operation mode
External operation
mode
Cannot be switched to PU operation mode
3, 4
External/PU combined operation mode
External/PU combined mode fixed
6
NET operation mode
External operation
mode
Operation mode can be switched with
operation continued
7
X12 (MRS)
ON
NET operation mode
External operation
mode
Output stop in External operation mode
X12 (MRS)
OFF
External operation mode
Forcibly switched to External operation mode
∗1
PU operation mode is selected when
Pr. 550 NET mode operation command source selection
= "0" (communication option command source) and the
communication option is not fitted.
∗2
PU operation mode is selected when the X16 signal is OFF. When the X65 signal has been assigned, the operation mode changes with the ON/
OFF state of the X65 signal.
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...