293
Causes and corrective actions
(2) Warnings
When a warning occurs, the output is not shut off.
Operation panel
indication
Er4
Name
Mode designation error
Description
Appears if a parameter setting is attempted in the External or NET operation mode with
Pr. 77
≠
"2".
Appears if a parameter setting is attempted when the command source is not at the operation panel.
Check point
Check that operation mode is PU operation mode.
Check the
Pr. 77
setting.
Check if FR Configurator (USB connector) or a parameter unit (FR-PU04/FR-PU07) is connected when
Pr. 551
=
"9999 (initial setting)."
Check the
Pr.551
setting.
Corrective action
After setting the operation mode to the "PU operation mode", make parameter setting.
After setting
Pr. 77
= "2", make parameter setting.
Disconnect FR Configurator (USB connector) or the parameter unit (FR-PU04/FR-PU07), and make parameter
setting.
After setting
Pr. 551
= "4", make parameter setting. (
Operation panel
indication
Err.
Name
Inverter reset
Description
Executing reset using RES signal, or reset command from communication or PU
Displays at powering OFF.
Corrective action
Turn OFF the reset command
Operation panel
indication
OL
FR-PU04
FR-PU07
OL
Name
Stall prevention (overcurrent)
Description
During
acceleration
When the output current (output torque when
Pr. 277 Stall prevention current switchover
= "1") of the
inverter exceeds the stall prevention operation level (
Pr. 22 Stall prevention operation level
, etc.), this
function stops the increase in frequency until the overload current decreases to prevent the inverter
from resulting in overcurrent trip. When the overload current has reduced below stall prevention
operation level, this function increases the frequency again.
During
constant-
speed
operation
When the output current (output torque when
Pr. 277 Stall prevention current switchover
= "1") of the
inverter exceeds the stall prevention operation level (
Pr. 22 Stall prevention operation level
, etc.), this
function reduces frequency until the overload current decreases to prevent the inverter from resulting
in overcurrent trip. When the overload current has reduced below stall prevention operation level, this
function increases the frequency up to the set value.
During
deceleration
When the output current (output torque when
Pr. 277 Stall prevention current switchover
= "1") of the
inverter exceeds the stall prevention operation level (
Pr. 22 Stall prevention operation level
, etc.), this
function stops the decrease in frequency until the overload current decreases to prevent the inverter
from resulting in overcurrent trip. When the overload current has decreased below stall prevention
operation level, this function decreases the frequency again.
Check point
Check that the
Pr. 0 Torque boost
setting is not too large.
Check that the
Pr. 7 Acceleration time
and
Pr. 8 Deceleration time
settings are not too small.
Check that the load is not too heavy.
Are there any failure in peripheral devices?
Check that the
Pr. 13 Starting frequency
is not too large.
Check that the
Pr. 22 Stall prevention operation level
is appropriate
Corrective action
Increase or decrease the
Pr. 0 Torque boost
setting 1% by 1% and check the motor status.
Set a larger value in
Pr. 7 Acceleration time
and
Pr. 8 Deceleration time
.
Reduce the load weight.
Try Advanced magnetic flux vector control and General-purpose magnetic flux vector control.
Change the
Pr. 14 Load pattern selection
setting.
Set stall prevention operation current in
Pr. 22 Stall prevention operation level
. (The initial value is 150%.) The
acceleration/deceleration time may change. Increase the stall prevention operation level with
Pr. 22 Stall prevention
operation level
, or disable stall prevention with
Pr. 156 Stall prevention operation selection
. (Operation at OL
occurrence can be selected using
Pr. 156
.)
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...