158
Monitor display and monitor output signal
(4) Cumulative power monitor and clear
(Pr. 170)
On the cumulative power monitor (
Pr. 52
= "25"), the output power monitor value is added up and is updated in 1h
increments.
The operation panel, parameter unit (FR-PU04/FR-PU07) and communication (RS-485 communication, communication
option) display increments and display ranges are as indicated below.
Writing "0" to
Pr. 170
clears the cumulative power monitor.
(5) Cumulative energization time and actual operation time monitor
(Pr. 171, Pr. 563, Pr. 564)
Cumulative energization time monitor (
Pr. 52
= "20") accumulates energization time from shipment of the inverter every
one hour.
On the actual operation time monitor (
Pr. 52
= "23"), the inverter running time is added up every hour. (Time is not added
up during a stop.)
If the monitored value exceeds 65535, it is added up from 0. You can check the numbers of cumulative energization time
monitor exceeded 65535h with
Pr. 563
and the numbers of actual operation time monitor exceeded 65535h with
Pr. 564
.
Writing "0" to
Pr. 171
clears the cumulative power monitor. (The cumulative time monitor can not be cleared.)
(6) You can select the decimal digits of the monitor
(Pr. 268)
As the operation panel display is 4 digits long, the decimal places may vary at analog input, etc. The decimal places can
be hidden by selecting the decimal digits.
In such a case, the decimal digits can be selected by
Pr. 268
.
Operation Panel
Parameter Unit
∗2
Communication
Range
Unit
Range
Unit
Range
Unit
Pr. 170
= 10
Pr. 170
= 9999
0 to 99.99kWh
0.01kWh
0 to 999.99kWh
0.01kWh
0 to 9999kWh
0 to 65535kWh
(initial value)
1kWh
100.0 to 999.9kWh
0.1kWh
1000.0 to 9999.9kWh
0.1kWh
1000 to 9999kWh
1kWh
10000 to 99999kWh
1kWh
∗1
Power is measured in the range 0 to 9999.99kWh, and displayed in 4 digits.
When the monitor value exceeds "99.99", a carry occurs, e.g. "100.0", so the value is displayed in 0.1kWh increments.
∗2
Power is measured in the range 0 to 99999.99kWh, and displayed in 5 digits.
When the monitor value exceeds "999.99", a carry occurs, e.g. "1000.0", so the value is displayed in 0.1kWh increments.
REMARKS
If "0" is written to
Pr. 170
and
Pr. 170
is read again, "9999" or "10" is displayed.
REMARKS
The actual operation time is not added up unless the inverter is operated one or more hours continuously.
If "0" is written to
Pr. 171
and
Pr. 171
is read again, "9999" is always displayed. Setting "9999" does not clear the actual operation
time meter.
Pr. 268
Setting
Description
9999 (initial value)
No function
0
For the first or second decimal places (0.1 increments or 0.01 increments) of the monitor, numbers in the first
decimal place and smaller are rounded to display an integral value (1 increments).The monitor value smaller than
0.99 is displayed as 0.
1
When 2 decimal places (0.01 increments) are monitored, the 0.01 decimal place is dropped and the monitor
displays the first decimal place (0.1 increments). The monitored digits in 1 increments are displayed as they are.
REMARKS
The number of display digits on the cumulative energization time (
Pr. 52
= "20"), actual operation time (
Pr. 52
= "23"), and
cumulative power (
Pr. 52
= "25") does not change.
Parameters referred to
Pr. 30 Regenerative function selection, Pr. 70 Special regenerative brake duty
Pr. 37 Speed display
Pr. 55 Frequency monitoring reference, Pr. 56 Current monitoring reference
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...