122
Selection and protection of a motor
(2) Setting
1) Select Advanced magnetic flux vector control (
) or General-purpose magnetic flux vector control (
2) Set "1" or "11" in
Pr. 96 Auto tuning setting/status
.
When the setting is "1" ....... Tune all motor constants without running the motor.
When performing Advanced magnetic flux vector control, set "1" to perform tuning.
It takes approximately 25 to 75s
∗
until tuning is completed.
(Excitation noise is produced during tuning.)
∗
Tuning time differs according to the inverter capacity and motor type.
When the setting is "11"...... Tune motor constants (R1) only without running the motor.
When performing General-purpose magnetic flux vector control, set "11" to perform
tuning.
It takes approximately 9s until tuning is completed.
3) Set the rated motor current (initial value is rated inverter current) in
Pr. 9
Electronic thermal O/L relay
. (
4) Set the rated voltage of motor (initial value is 200V/400V) in
Pr. 83 Rated motor voltage
and rated motor frequency (initial
value is 60Hz) in
Pr. 84 Rated motor frequency
.
(For a Japanese standard motor, etc. which has both 50Hz and 60Hz rated values, use it with an initial value (200V/60Hz
or 400V/60Hz).
5) Set
Pr. 71 Applied motor
according to the motor used.
Motor
Pr. 71
Setting
Mitsubishi standard motor
Mitsubishi high efficiency motor
SF-JR
3
SF-JR 4P 1.5kW or less
23
SF-HR
43
Others
3
Mitsubishi constant-torque motor
SF-JRCA 4P
13
SF-HRCA
53
Others (SF-JRC, etc.)
13
Other manufacturer's
standard motor
—
3
Other manufacturer's
constant-torque motor
—
13
∗1
for other settings of
Pr. 71
.
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...