109
Setting of acceleration/deceleration time and acceleration/ deceleration pattern
4.8 Setting of acceleration/deceleration time and acceleration/
deceleration pattern
4.8.1
Setting of the acceleration and deceleration time
(Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45, Pr. 147)
Purpose
Parameter that should be Set
Refer to Page
Motor acceleration/deceleration
time setting
Acceleration/deceleration
times
Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44,
Pr. 45, Pr. 147
Starting frequency
Starting frequency and
start-time hold
Pr. 13, Pr. 571
Set acceleration/deceleration
pattern suitable for application
Acceleration/deceleration
pattern
Pr. 29
Automatically set optimum
acceleration/deceleration time.
Automatic acceleration/
deceleration
Pr. 61 to Pr. 63, Pr. 292
Used to set motor acceleration/deceleration time.
Set a larger value for a slower speed increase/decrease or a smaller value for a faster speed increase/decrease.
For the acceleration time at automatic restart after instantaneous power failure, refer to
Pr. 611 Acceleration time at a
restart (page 162).
Parameter
Number
Name
Initial Value
Setting
Range
Description
7
Acceleration time
3.7K or less
5s
0 to 3600/
360s
Motor acceleration time.
5.5K, 7.5K
10s
11K, 15K
15s
8
Deceleration time
3.7K or less
5s
0 to 3600/
360s
∗2
Motor deceleration time.
5.5K, 7.5K
10s
11K, 15K
15s
20
Acceleration/
deceleration
reference
frequency
60Hz
1 to 400Hz
Frequency that will be the basis of
acceleration/deceleration time.
As acceleration/deceleration time, set the
frequency change time from stop to
Pr. 20
.
21
Acceleration/
deceleration time
increments
0
0
Increments: 0.1s
Range: 0 to
3600s
Increments and setting
range of acceleration/
deceleration time
setting can be
changed.
1
Increments: 0.01s
Range: 0 to 360s
44
Second
acceleration/
deceleration time
3.7K or less
5s
0 to 3600/
∗2
Acceleration/deceleration time when the RT
signal is ON.
5.5K, 7.5K
10s
11K, 15K
15s
45
Second
deceleration time
9999
0 to 3600/
360s
∗2
Deceleration time when the RT signal is
ON.
9999
Acceleration time = deceleration time
147
Acceleration/
deceleration time
switching
frequency
9999
0 to 400Hz
Frequency when automatically switching to
the acceleration/deceleration time of
Pr. 44
and
Pr. 45
.
9999
No function
∗1
The above parameters can be set when
Pr. 160 User group read selection
= "0".
∗2
Depends on the
Pr. 21 Acceleration/deceleration time increments
setting. The initial value for the setting range is "0 to 3600s" and the setting increments is "0.1s".
.............Specifications differ according to the date assembled.
to check the SERIAL number.
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...