314
Inspection items
6.1.4
Display of the life of the inverter parts
The self-diagnostic alarm is output when the life span of the control circuit capacitor, cooling fan and each parts of the inrush
current limit circuit is near its end. It gives an indication of replacement time.
The life alarm output can be used as a guideline for life judgement.
Parts
Judgement Level
Main circuit capacitor
85% of the initial capacity
Control circuit capacitor
Estimated remaining life 10%
Inrush current limit circuit
Estimated remaining life 10%
(Power on: 100,000 times left)
Cooling fan
Less than 50% of the predetermined speed