241
Communication operation and setting
(6) Modbus registers
System environment variable
∗1
The communication parameter values are not cleared.
∗2
For write, set the data as a control input instruction.
For read, data is read as an inverter operating status.
∗3
For write, set data as the operation mode setting.
For read, data is read as the operation mode status.
Real time monitor
Refer to page 154 for details of the monitor description
.
.......Specifications differ according to the date assembled.
to check the SERIAL number.
Register
Definition
Read/write
Remarks
40002
Inverter reset
Write
Any value can be written
40003
Parameter clear
Write
Set H965A as a written value.
40004
All Parameter clear
Write
Set H99AA as a written value.
40006
Parameter clear
∗1
Write
Set H5A96 as a written value.
40007
All parameter clear
∗1
Write
Set HAA99 as a written value.
40009
Inverter status/control input instruction
Read/write
See below.
40010
Operation mode/inverter setting
Read/write
See below.
40014
Running frequency (RAM value)
Read/write
According to the
Pr.37
settings, the frequency
and selectable speed are in 1r/min
increments.
40015
Running frequency (EEPROM value)
Write
<
Inverter status/control input instruction
>
∗1
The signal within parentheses is the default setting. The description changes depending on the setting of
Pr.180 to Pr.184 (input terminal function
selection)
.
Each assigned signal is valid or invalid depending on NET.
∗2
The signal within parentheses is the default setting. Definitions change according to the
Pr.190 to Pr.192 (output terminal function selection)
.
Bit
Definition
Control input instruction
Inverter status
0
Stop command
RUN (inverter running)
1
Forward rotation command
Forward rotation
2
Reverse rotation command
During reverse rotation
3
RH (high-speed operation
command)
SU (up-to-frequency)
4
RM (middle-speed operation
command)
OL (overload)
5
RL (low-speed operation
command)
0
6
0
FU (frequency detection)
∗2
7
RT (second function selection)
ABC (fault)
∗2
8
AU (current input selection)
0
9
0
0
10
MRS (output stop)
0
11
0
0
12
RES (reset)
0
13
0
0
14
0
0
15
0
Fault occurrence
<
Operation mode/inverter setting
>
The restrictions depending on the operation
mode changes according to the computer
link specifications.
Mode
Read Value
Written
Value
EXT
H0000
H0010
PU
H0001
—
EXT
JOG
H0002
—
PU
JOG
H0003
—
NET
H0004
H0014
PU+EXT
H0005
—
Register
Description
Unit
40201
Output frequency/speed
∗1
0.01Hz/1
40202
Output current
0.01A
40203
Output voltage
0.1V
40205
Output frequency setting/speed
setting
∗1
0.01Hz/1
40207
Motor torque
0.1%
40208
Converter output voltage
0.1V
40209
Regenerative brake duty
0.1%
40210
Electronic thermal relay function
load factor
0.1%
40211
Output current peak value
0.01A
40212
Converter output voltage peak value
0.1V
40214
Output power
0.01kW
40215
Input terminal status
—
40216
Output terminal status
∗3
—
40220
Cumulative energization time
1h
40223
Actual operation time
1h
40224
Motor load factor
0.1%
40225
Cumulative power
1kWh
40252
PID set point
0.1%
40253
PID measured value
0.1%
40254
PID deviation
0.1%
40258
Option input terminal status
—
40259
Option input terminal status 2
—
40260
Option output terminal status
∗6
—
40261
Motor thermal load factor
0.1%
40262
Inverter thermal load factor
0.1%
40263
Cumulative power 2
0.01kWh
Register
Description
Unit
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...