Special operation and frequency control
(5) PID automatic switchover control
(Pr. 127)
The system can be started up without PID control only at a start.
When the frequency is set to
Pr. 127 PID control automatic switchover frequency
within the range 0 to 400Hz, the inverter
starts up without PID control from a start until output frequency is reached to the set frequency of
Pr. 127
, and then it shifts
to PID control. Once the system has entered PID control operation, it continues PID control if the output frequency falls to
or below
Pr.127
.
(6) PID monitor function
The PID control set point, measured value and deviation value can be displayed on the operation panel and output from
terminal FM.
Integral value indicating a negative % can be displayed on the deviation monitor. 0% is displayed as 1000. (The deviation
monitor cannot be output from the terminal FM.)
For each monitor, set the following value in
Pr. 52 DU/PU main display data selection
and
Pr. 54 FM terminal function selection
.
Setting
Monitor Description
Minimum
Increments
Terminal FM Full
Scale
Remarks
52
PID set point
0.1%
100%
—
53
PID measured value
0.1%
100%
54
PID deviation
0.1%
—
Value cannot be set to
Pr. 54
.
Displays 1000 when the PID deviation is 0%.
Output frequency
Pr. 127
STF
Time
PID
Without
PID control
PID control
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...