31
Control circuit specifications
2.3.4
Safety stop function (available only for the safety stop function model)
(1) Description of the function
The terminals related to the safety stop function are shown below.
∗1
In the initial status, terminal S1 and S2 are shorted with terminal PC by shortening wire. Remove the shortening wire and connect the safety relay module
when using the safety stop function.
∗2
In the initial setting, output frequency detection (FU signal) is assigned to terminal FU. Set "80" to
Pr.191 FU terminal function selection
to assign SAFE signal.
The function can be assigned to other terminals by setting "80 (positive logic) or 180 (negative logic)" to any of
Pr.190 to Pr.192 (Output terminal function
selection)
. (
∗3
In the initial setting, inverter running (RUN signal) is assigned to terminal RUN. Set "81" to
Pr.190 RUN terminal function selection
to assign SAFE2 signal. The
function can be assigned to other terminals by setting "81 (positive logic) or 181 (negative logic)" to any of
Pr.190 to Pr.192 (Output terminal function selection)
.
∗4
At an internal safety circuit failure, one of E.SAF, E.6, E.7, and E.CPU is displayed on the operation panel.
.....
Specifications differ according to the date assembled.
to check the SERIAL number.
(2) Wiring connection diagram
To prevent restart at fault occurrence, connect terminals RUN (SAFE 2 signal) and SE to terminals XS0 and XS1, which are
the feedback input terminals of the safety relay module.
By setting
Pr. 190 RUN terminal function selection
= "81 (SAFE2 signal)", terminal RUN is turned OFF at fault occurrence.
Terminal Symbol
Description
S1
For input of safety stop channel 1.
Between S1 and PC / S2 and PC
Open: In safety stop state.
Short: Other than safety stop state.
S2
For input of safety stop channel 2.
PC
Common terminal for terminal S1 and S2.
FU
SAFE
signal
Outputs the safety stop status
The signal is output when inverter output is shut off due to the
safety stop function.
OFF: Drive enabled or drive stop (at an internal
safety circuit failure
ON: Drive stop (no internal safety circuit failure
)
RUN
SAFE2
signal
Outputs when an alarm or failure is detected.
The signal is output when no internal safety circuit failure
exists.
OFF: Internal safety circuit failure
ON : No internal safety circuit failure
SE
Common terminal for open collector outputs (terminal RUN and FU)
NOTE
y
Hold the ON or OFF status for 2ms or longer to input signal to terminal S1 or S2. Signal input shorter than 2ms is not
recognized.
y
Use SAFE signal to monitor safety stop status. SAFE signal cannot be used as safety stop input signal to other
devices (other than the safety relay module).
y
SAFE 2 signal can only be used to output an alarm or to prevent restart of an inverter. The signal cannot be used as
safety stop input signal to other devices.
NOTE
y
Changing the terminal assignment using
Pr. 190 to Pr. 192 (output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
S2
S1
PC
Inverter
START/RESET
+24V
QS90SR2SN-Q
K1
X0
X1
COM0
COM1
24G
XS0
XS1
Z10
Z00
Z20
Z11
Z01
Z21
K2
DC24V
RUN(SAFE2)
R S T
U V W
MITSUBISHI MELSEC Safety relay module
IM
SE
STF
STR(STOP)
STF
STOP
SD
I/O control
FU(SAFE)
monitor
*1
*1
*2
*2
Internal
Safety
Circuit
Output shutoff
circuit
*1 Output signals differ by the setting of
Pr.190 and
Pr.191 (Output terminal function selection)
.
*2 Input signals differ by the setting of
Pr178 to Pr.182
(Input terminal function selection)
.
Emergency
stop button
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...