171
Operation setting at fault occurrence
Using
Pr. 65
, you can select the fault that will cause a retry to be executed. No retry will be made for the fault not indicated.
(
for the fault description.)
indicates the faults selected for retry.
NOTE
When terminal assignment is changed using
Pr.190 to Pr.192
, the other functions may be affected. Set parameters after
confirming the function of each terminal.
The data stored as the error reset for retry is only that of the fault which occurred the first time.
When an inverter fault is reset by the retry function at the retry time, the accumulated data of the electronic thermal
relay function, regeneration brake duty etc. are not cleared. (Different from the power-ON reset.)
Retry is not performed if E.PE (Parameter storage device fault) occurred at power ON.
If a fault that is not selected for a retry occurs during retry operation (retry waiting time), the retry operation stops
while the fault indication is still displayed.
CAUTION
When you have selected the retry function, stay away from the motor and machine when the inverter is
tripped. They will start suddenly (after the reset time has elapsed) after the inverter trip.
When you have selected the retry function, apply in easily visible places the CAUTION stickers supplied.
Parameters referred to
Pr. 57 Restart coasting time
(
Fault for
Retry
Pr. 65
Setting
0
1
2
3
4
5
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E. BE
E. GF
E.USB
E.OHT
E.OLT
E.OPT
E.OP1
E. PE
E.MB4
E.MB5
E.MB6
E.MB7
E.ILF
Fault for
Retry
Pr. 65
Setting
0
1
2
3
4
5
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...