EMC and leakage currents
3.1.4
Harmonic suppression guideline in Japan
Harmonic currents flow from the inverter to a power receiving point via a power transformer. The harmonic suppression
guideline was established to protect other consumers from these outgoing harmonic currents.
The three-phase 200V input specifications 3.7kW or less (single-phase 200V power input model 2.2kW or less, single-phase
100V power input model 0.75kW) are previously covered by "Harmonic suppression guideline for household appliances and
general-purpose products" and other models are covered by "Harmonic suppression guideline for consumers who receive
high voltage or special high voltage". However, the transistorized inverter has been excluded from the target products covered
by "Harmonic suppression guideline for household appliances and general-purpose products" in January 2004 and "Harmonic
suppression guideline for household appliances and general-purpose products" was repealed on September 6, 2004.
All capacity and all models of general-purpose inverter used by specific consumers are covered by "Harmonic suppression
guideline for consumers who receive high voltage or special high voltage" (hereinafter referred to as "Guideline for specific
consumers").
"Guideline for specific consumers"
This guideline sets forth the maximum values of harmonic currents outgoing from a high-voltage or especially high-voltage
consumer who will install, add or renew harmonic generating equipment. If any of the maximum values is exceeded, this
guideline requires that consumer to take certain suppression measures.
(1) Application for specific consumers
Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power
Received Power Voltage
5th
7th
11th
13th
17th
19th
23rd
Over 23rd
6.6kV
3.5
2.5
1.6
1.3
1.0
0.9
0.76
0.70
22kV
1.8
1.3
0.82
0.69
0.53
0.47
0.39
0.36
33kV
1.2
0.86
0.55
0.46
0.35
0.32
0.26
0.24
Table 2 Conversion Factors for FR-E700 Series
Class
Circuit Type
Conversion Factor (Ki)
3
Three-phase bridge
(Capacitor smoothing)
Without reactor
K31= 3.4
With reactor (AC side)
K32 = 1.8
With reactor (DC side)
K33 = 1.8
With reactors (AC, DC sides)
K34 = 1.4
4
Single-phase bridge
(Capacitor smoothing)
Without reactor
K41= 2.3
With reactor (AC side)
K42 = 0.35 *
5
Self-excitation three-phase bridge
When high power factor converter is used
K5 = 0
∗
K42=0.35 is a value when the reactor value is 20%. Since a 20% reactor is large and considered to be not practical, K42=1.67 is written as conversion
factor for a 5% reactor in the technical data JEM-TR201 of The Japan Electrical Manufacturers' Association and this value is recommended for calculation
for the actual practice.
Table 3 Equivalent Capacity Limits
Received Power Voltage
Reference Capacity
6.6kV
50kVA
22/33 kV
300kVA
66kV or more
2000kVA
Install, add or renew
equipment
Calculation of equivalent
capacity total
Equal to or less
than reference
capacity
Equivalent
capacity total
Above reference
capacity
Calculation of outgoing
harmonic current
Not more than
harmonic current upper
limit?
Equal to or less
than upper limit
Harmonic suppression
measures unnecessary
More than upper limit
Harmonic suppression
measures necessary
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...