254
Special operation and frequency control
132
PID lower limit
9999
0 to 100%
Minimum value
If the process value falls below the setting
range, the FDN signal is output. The
maximum input (20mA/5V/10V) of the
measured value (terminal 4) is equivalent
to 100%.
9999
No function
133
∗1
PID action set
point
9999
0 to 100%
Used to set the set point for PID control.
9999
Always 50%
134
∗1
PID differential
time
9999
0.01 to 10.00s
For deviation ramp input, time (Td) required
for providing only the manipulated variable
for the proportional (P) action.
As the differential time increases, greater
response is made to a deviation change.
9999
No differential control.
The above parameters can be set when
Pr.160 User group read selection
="0".
∗1
This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection
.
Parameter
Number
Name
Initial Value
Setting
Range
Description