188
Misoperation prevention and parameter setting restriction
4.18.3 Reverse rotation prevention selection (Pr. 78)
Set this parameter when you want to limit the motor rotation to only one direction.
This parameter is valid for all of the reverse rotation and forward rotation keys of the operation panel and parameter
unit(FR-PU04/FR-PU07), the start signals (STF, STR signals) via external terminals, and the forward and reverse rotation
commands through communication.
4.18.4 Extended parameter display and user group function (Pr. 160, Pr. 172 to Pr. 174)
(1) Display of simple mode parameters and extended parameters
(Pr. 160)
When
Pr. 160
= "9999", only the simple mode parameters can be displayed on the operation panel and parameter unit (FR-
PU04/FR-PU07). (Refer to the parameter list
, page 62
, for the simple mode parameters.)
In the initial setting (
Pr. 160
= "0") status, simple mode parameters and extended parameters can be displayed.
This function can prevent reverse rotation fault resulting from the incorrect input of the start signal.
Parameter
Number
Name
Initial
Value
Setting Range
Description
78
Reverse rotation prevention
selection
0
0
Both forward and reverse rotations allowed
1
Reverse rotation disabled
2
Forward rotation disabled
The above parameters can be set when
Pr. 160 User group read selection
= "0".
Parameter which can be read from the operation panel and parameter unit can be restricted.
Parameter
Number
Name
Initial
Value
Setting Range
Description
160
∗3
User group read selection
0
9999
Displays only the simple mode parameters
0
Displays simple mode + extended parameters
1
Displays the parameters registered in the user
group.
172
∗1
User group registered
display/batch clear
0
(0 to 16)
Displays the number of cases registered as a
user group (reading only)
9999
Batch clear the user group registration
173
User group registration
9999
0 to 999, 9999
Sets the parameter numbers to be registered to
the user group
174
User group clear
9999
0 to 999, 9999
Sets the parameter numbers to be cleared from
the user group
∗1
The above parameters can be set when
Pr. 160 User group read selection
= "0".
∗2
The values read from
Pr. 173 and Pr. 174
are always "9999".
∗3
This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in
Pr. 77 Parameter write selection
.
REMARKS
When a plug-in option is fitted to the inverter, the option parameters can also be read.
When communication is used to read the parameters, all parameters can be read, regardless of the
Pr. 160
setting.
Pr. 15 Jog frequency
,
Pr. 16 Jog acceleration/deceleration time
, and
Pr. 991 PU contrast adjustment
are displayed as simple mode
parameter when the parameter unit (FR-PU04/FR-PU07) is fitted.
When RS-485 communication is used to read the
parameters, all parameters can be read,
regardless of the
Pr. 550 NET mode operation
command source selection
,
Pr. 551 PU mode operation
command source selection
, regardless of
Pr. 160
setting.
∗
OP indicates a communication option.
Pr. 551
Pr. 550
Pr. 160
Valid/Invalid
2 (PU)
-
Valid
3 (USB)
9999
(auto detect initial
value)
0 (OP)
Valid
2 (PU)
Invalid (all parameters
can be read)
9999
(auto detect initial
value)
With OP: valid
Without OP: invalid
(all parameters can be
read)
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...