Parameter list
Parameter list
62
Parameter List
4.2 Parameter list
4.2.1
Parameter list
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check are available
from the operation panel.
y
Symbol in the Remarks columm.
... Specifications differ according to the date assembled.
to check the SERIAL number.
y
Symbols in the table indicate parameters which function when an option is mounted.
......... FR-A7AX E kit,
..... FR-A7AY E kit,
....... FR-A7AR E kit,
.... FR-A7NC E kit,
.... FR-A7ND E kit,
......FR-A7NL E kit,
......... FR-A7NP E kit
y
These instruction codes are used for parameter read and write by using Mitsubishi inverter protocol with the RS-485 communication.
(
for RS-485 communication)
y
"
{
" indicates valid and "
×
" indicates invalid of "control mode-based correspondence table", "parameter copy", "parameter clear", and "all parameter clear".
Func-
tion
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Parameter
Remarks
Instruction Code
Control Mode-based
Correspondence Table
Parameter
Read
Write
Extended
Copy
Clear
All clear
Basi
c functi
ons
0
Torque boost
0 to 30%
0.1%
6/4/3/2%
∗1
0
00
80
0
{
×
×
{
{
{
1
Maximum frequency
0 to 120Hz
0.01Hz
120Hz
1
01
81
0
{
{
{
{
{
{
2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
2
02
82
0
{
{
{
{
{
{
3
Base frequency
0 to 400Hz
0.01Hz
60Hz
3
03
83
0
{
×
×
{
{
{
4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
4
04
84
0
{
{
{
{
{
{
5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
5
05
85
0
{
{
{
{
{
{
6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
6
06
86
0
{
{
{
{
{
{
7
Acceleration time
0 to 3600/360s
0.1/0.01s
5/10/15s
∗2
7
07
87
0
{
{
{
{
{
{
8
Deceleration time
0 to 3600/360s
0.1/0.01s
5/10/15s
∗2
8
08
88
0
{
{
{
{
{
{
9
Electronic thermal O/L relay
0 to 500A
0.01A
Rated
inverter
current
9
09
89
0
{
{
{
{
{
{
DC injection
br
ake
10
DC injection brake operation frequency 0 to 120Hz
0.01Hz
3Hz
10
0A
8A
0
{
{
{
{
{
{
11
DC injection brake operation time
0 to 10s
0.1s
0.5s
11
0B
8B
0
{
{
{
{
{
{
12
DC injection brake operation voltage
0 to 30%
0.1%
6/4/2%
∗3
12
0C
8C
0
{
{
{
{
{
{
—
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
13
0D
8D
0
{
{
{
{
{
{
—
14
Load pattern selection
0 to 3
1
0
14
0E
8E
0
{
×
×
{
{
{
JO
G
operat
ion
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
15
0F
8F
0
{
{
{
{
{
{
16
Jog acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
0.5s
16
10
90
0
{
{
{
{
{
{
—
17
MRS input selection
0, 2, 4
1
0
17
11
91
0
{
{
{
{
{
{
—
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120Hz
18
12
92
0
{
{
{
{
{
{
—
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999
19
13
93
0
{
×
×
{
{
{
Acc
e
le
rati
on
/
deceleration time
20
Acceleration/deceleration reference
frequency
1 to 400Hz
0.01Hz
60Hz
20
14
94
0
{
{
{
{
{
{
21
Acceleration/deceleration time
increments
0, 1
1
0
21
15
95
0
{
{
{
{
{
{
St
al
l
prevention
22
Stall prevention operation level
0 to 200%
0.1%
150%
22
16
96
0
{
{
{
{
{
{
23
Stall prevention operation level
compensation factor at double speed
0 to 200%, 9999
0.1%
9999
23
17
97
0
{
{
{
{
{
{
Mu
lti-speed
setting
24
Multi-speed setting (speed 4)
0 to 400Hz, 9999
0.01Hz
9999
24
18
98
0
{
{
{
{
{
{
25
Multi-speed setting (speed 5)
0 to 400Hz, 9999
0.01Hz
9999
25
19
99
0
{
{
{
{
{
{
26
Multi-speed setting (speed 6)
0 to 400Hz, 9999
0.01Hz
9999
26
1A
9A
0
{
{
{
{
{
{
27
Multi-speed setting (speed 7)
0 to 400Hz, 9999
0.01Hz
9999
27
1B
9B
0
{
{
{
{
{
{
—
29
Acceleration/deceleration pattern
selection
0, 1, 2
1
0
29
1D
9D
0
{
{
{
{
{
{
REMARKS
y
indicates simple mode parameters. (initially set to extended mode)
y
The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in
Pr. 77 Parameter write selection
.
V/F
V/F
V/F
AD MFVC
AD MFVC
AD MFVC
GP MFVC
GP MFVC
GP MFVC
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...