258
Special operation and frequency control
(5) Parameter details
When ratio (
Pr. 128
= "42, 43") is selected for addition method, PID
control
×
(ratio of main speed) is added to the main speed. The ratio is
determined by the
Pr. 125
Terminal 2 frequency setting gain frequency
and
C2 (Pr. 902)
Terminal 2 frequency setting bias frequency
. The frequency
setting signal is set to 0 to 60Hz in the range between 0 to 100% in the
initial setting. The ratio is (
×
100%) when the main speed is 60Hz and
(
×
50%) when 30Hz.
Turning X14 signal ON/OFF during operation by assigning X14 signal results in the following operation.
When X14 signal is ON: Uses output frequency unchanged as the main speed command and continues operation by
dancer control.
When X14 signal is OFF: Ends dancer control and continues operation at the set frequency.
Action of
Pr. 129 PID proportional band, Pr. 130 PID integral time, Pr. 131 PID upper limit, Pr. 132 PID lower limit, Pr. 134 PID
differential time
is the same as PID control. For the relationship of controlled variable (%) of PID control and frequency, 0%
is equivalent to the set frequency of
Pr. 902
and 100% to
Pr. 903
.
For the
Pr. 133 PID action set point
setting, set frequency of
Pr. 902
is equivalent to 0% and
Pr. 903
to 100%. When
9999
is
set in
Pr. 133
, 50% is the set point.
(6) Output signal
Output terminal assignment during dancer control (PID control) operation
PID signal turns ON during dancer control (PID control) or at a stop by PID control (in the status PID operation being
performed inside) (The signal is OFF during normal operation.)
For the terminal used for PID signal output, assign the function by setting "47 (positive logic) or 147 (negative logic)" in any
of
Pr. 190
to
Pr. 192 (output terminal function selection)
.
(7) PID monitor function
The PID control set point and measured value can be output to the operation panel monitor display and terminal FM.
For each monitor, set the following value in
Pr. 52 DU/PU main display data selection
and
Pr. 54 FM terminal function selection
.
(8) Priorities of main speed command
The priorities of the main speed speed command source when the speed command source is external are as follows.
JOG
signal
>
multi-speed setting signal (RL/RM/RH/REX)
>
16 bit digital input (option)
>
terminal 2
The priorities of the main speed speed command source when "3" is set in
Pr. 79
.
Multi-speed setting signal (RL/RM/RH/REX)
>
set frequency (digital setting by PU, operation panel)
Terminal 4 can not be selected as the main speed speed command even when AU terminal is turned ON.
Even when a remote operation function is selected by setting a value other than "0" in
Pr. 59
, compensation of the remote
setting frequency to the main speed is ignored (changes to 0).
NOTE
Even when
C4 (Pr. 903)
is set to other than 100%, the frequency setting signal is considered as 100%.
Even when
C3 (Pr. 903)
is set to other than 0%, the frequency setting signal is considered as 0%.
When
C2 (Pr .902
) is set to other than 0Hz, the frequency setting signal is 0% when
C2 (Pr. 902)
is less than the set
frequency.
Pr. 128
Setting
PID Action
Addition
Method
Set Point
Measured
Value
Main Speed Command
40
Reverse action
Fixed
Pr. 133
Terminal 4
Speed command for each
operation mode
41
Forward action
42
Reverse action
Ratio
43
Forward action
REMARKS
Pr. 127 PID control automatic switchover frequency
is invalid.
NOTE
Changing the terminal function using any of
Pr. 178
to
Pr. 184, Pr. 190
to
Pr. 192
may affect the other functions. Set
parameters after confirming the function of each terminal.
Setting
Monitor Description
Minimum
Increments
Terminal FM Full
Scale
Remarks
52
PID set point
0.1%
100%
—
53
PID measured value
0.1%
100%
54
PID deviation value
0.1%
—
Value cannot be set in
Pr. 54
.
Displays 1000 when the PID deviation is 0%.
C2(Pr. 902)
Output frequency
0
Frequency setting signal
100%
Initial value
Bias
Pr. 125
Gain
60Hz
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...