EMC and leakage currents
3.1 EMC and leakage currents
3.1.1
Leakage currents and countermeasures
Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current
flows. Since its value depends on the static capacitances, carrier frequency, etc., low acoustic noise operation at the
increased carrier frequency of the inverter will increase the leakage current. Therefore, take the following measures. Select
the earth leakage current breaker according to its rated sensitivity current, independently of the carrier frequency setting.
(1) To-earth (ground) leakage currents
Leakage currents may flow not only into the inverter's own line but also into the other lines through the earthing cable, etc.
These leakage currents may operate earth (ground) leakage circuit breakers and earth leakage relays unnecessarily.
Suppression technique
If the carrier frequency setting is high, decrease the
Pr. 72 PWM frequency selection
setting.
Note that motor noise increases. Selecting
Pr. 240 Soft-PWM operation selection
makes the sound inoffensive.
By using earth leakage circuit breakers designed for harmonic and surge suppression in the inverter's own line and other
line, operation can be performed with the carrier frequency kept high (with low noise).
To-earth (ground) leakage currents
Take caution as long wiring will increase the leakage current. Decreasing the carrier frequency of the inverter reduces the
leakage current.
Increasing the motor capacity increases the leakage current. The leakage current of the 400V class is larger than that of
the 200V class.
(2) Line-to-line leakage currents
Harmonics of leakage currents flowing in static capacitances between the inverter output cables may operate the external
thermal relay unnecessarily. When the wiring length is long (50m or more) for the 400V class small-capacity model (7.5kW(SC)
or less), the external thermal relay is likely to operate unnecessarily because the ratio of the leakage current to the rated motor
current increases.
Line-to-line leakage current data example (200V class)
*The leakage currents of the 400V class are about twice as large.
Measures
Use
Pr. 9 Electronic thermal O/L relay
.
If the carrier frequency setting is high, decrease the
Pr. 72 PWM frequency selection
setting.
Note that motor noise increases. Selecting
Pr. 240 Soft-PWM operation selection
makes the sound inoffensive.
To ensure that the motor is protected against line-to-line leakage currents, it is recommended to use a temperature
sensor to directly detect motor temperature.
Installation and selection of moulded case circuit breaker
Install a moulded case circuit breaker (MCCB) on the power receiving side to protect the wiring of the inverter input side.
Select the MCCB according to the inverter input side power factor (which depends on the power supply voltage, output
frequency and load). Especially for a completely electromagnetic MCCB, one of a slightly large capacity must be selected
since its operation characteristic varies with harmonic currents. (Check it in the data of the corresponding breaker.) As an
earth leakage current breaker, use the Mitsubishi earth leakage current breaker designed for harmonics and surge
suppression.
Motor Capacity
(kW)
Rated Motor
Current (A)
Leakage Current (mA)
*
Wiring length 50m
Wiring length 100m
0.4
1.8
310
500
0.75
3.2
340
530
1.5
5.8
370
560
2.2
8.1
400
590
3.7
12.8
440
630
5.5
19.4
490
680
7.5
25.6
535
725
Motor: SF-JR 4P
Carrier frequency: 14.5kHz
Used wire: 2mm
2
, 4 cores
Cabtyre cable
Power
supply
Thermal relay
Line-to-line static
capacitances
MCCB
MC
Line-to-line leakage currents path
Motor
Inverter
IM
Содержание FR-E710W-0.1K
Страница 49: ...40 MEMO ...
Страница 65: ...56 MEMO ...
Страница 288: ...288 MEMO ...
Страница 310: ...310 MEMO ...
Страница 334: ...334 MEMO ...
Страница 335: ...335 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 348: ...4 4 BCN C22005 679 MEMO BCN C22005 679 fm 4 ページ 2014年11月7日 金曜日 午前11時58分 ...