118
Function assignment of external terminal and control
(1) Input terminal function assignment
Using
Pr. 178 to Pr. 182
, set the functions of the input terminals.
Refer to the following table and set the parameters:
When
Pr. 59 Remote function selection
"0", the functions of the RL, RM and RH signals are changed as given in the table.
The OH signal turns ON when the relay contact "opens".
(2) Response time of each signal
The response time of the X10 signal and MRS signal is within 2ms.
The response time of other signals is within 20ms.
Setting
Signal
Function
Related Parameters
Refer to
Page
0
RL
Pr. 59
= 0 (initial value)
Low-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
0
Remote setting (setting clear)
Pr. 59
1
RM
Pr. 59
= 0 (initial value)
Middle-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
0
Remote setting (deceleration)
Pr. 59
2
RH
Pr. 59
= 0 (initial value)
High-speed operation command
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 59
0
Remote setting (acceleration)
Pr. 59
3
RT
Second function selection
Pr. 44, Pr. 45, Pr. 48
4
AU
Terminal 4 input selection
Pr. 267
5
JOG
Jog operation selection
Pr. 15, Pr. 16
7
OH
External thermal relay input
Pr. 9
8
REX
15-speed selection (combination with three speeds RL, RM, RH)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
10
X10
Drive unit run enable signal (FR-HC2, FR-CV connection)
Pr. 30, Pr. 70
12
X12
PU operation external interlock
Pr. 79
14
X14
PID control valid terminal
Pr. 127 to Pr. 134
16
X16
PU/External operation switchover (turning ON X16 selects External
operation)
Pr. 79, Pr. 340
23
LX
Pre-excitation
Pr. 11, Pr. 795
24
MRS
Output stop
Pr. 17
25
STOP
Start self-holding selection
—
60
STF
Forward rotation command (assigned to STF terminal
(Pr. 178)
only) —
61
STR
Reverse rotation command (assigned to STR terminal
(Pr. 179)
only) —
62
RES
Drive unit reset
—
—
64
X64
PID forward/reverse action switchover
Pr. 127 to Pr. 134
65
X65
PU/NET operation switchover (turning ON X65 selects PU
operation)
Pr. 79, Pr. 340
66
X66
External/NET operation switchover (turning ON X66 selects NET
operation)
Pr. 79, Pr. 340
67
X67
Command source switchover (turning ON X67 makes
Pr. 338
and
Pr.
339
commands valid)
Pr. 338, Pr. 339
72
X72
PID integral value reset
Pr. 127 to Pr. 134, Pr. 553,
Pr. 554, Pr. 575 to Pr. 577,
C42 to C45
9999
—
No function
—
—
NOTE
Changing the terminal assignment using
Pr. 178 to Pr. 182 (input terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
The priorities of the speed commands are in order of jog > multi-speed setting (RH, RM, RL, REX) > PID (X14).
When the X10 signal (FR-HC2, FR-CV connection-drive unit operation enable signal) is not set or when the PU
operation external interlock (X12) signal is not assigned with
Pr. 79 Operation mode selection
set to "7", the MRS signal
shares this function.
Same signal is used to assign multi-speed (7 speeds) and remote setting. These cannot be set individually.
(Same signal is used since multi-speed (7 speeds) setting and remote setting are not used to set speed at the same
time.)
Turning the AU signal ON makes terminal 2 (voltage input) invalid.