217
Special operation and speed control
577
Output interruption
cancel level
1000%
900 to 1100%
Set the level (
Pr. 577
minus 1000%) at which the PID output
interruption function is canceled.
C42
(934)
PID display bias
coefficient
9999
0 to 500.00
Set the coefficient on bias (minimum) side of terminal 4 input.
9999
Displayed in %.
C43
(934)
PID display bias
analog value
20%
0 to 300.0%
Set the converted % on bias (minimum) side current /voltage of
terminal 4 input.
C44
(935)
PID display gain
coefficient
9999
0 to 500.00
Set the coefficient on gain (maximum) side of the terminal 4 input.
9999
Displayed in %.
C45
(935)
PID display gain
analog value
100%
0 to 300.0%
Set the converted % on gain (maximum) side of current/voltage of
terminal 4 input.
The above parameters can be set when
Pr. 160 Extended function display selection
=
"0".
Pr. 129, Pr. 130, Pr. 133
and
Pr. 134
can be set during operation. These can also be set independently of the operation mode.
The value left of the slash is for the 2.2K drive unit or lower. The one right of the slash is for the 3.7K drive unit.
If a value exceeding the upper speed limit of the motor is set, the actual operation will be limited at the maximum rotation speed. The setting range is for the
S-PM motor. The maximum setting value differs depending on the number of poles of the applied motor.
If
C42 (Pr. 934)
and
C44 (Pr. 935)
are both set to values other than "9999", the setting range for
Pr. 131 to Pr. 133
and
Pr. 553
become only "9999", and % is
not displayed in the setting range of
Pr. 577
. (Values set in
Pr. 553
and
Pr. 577
are converted as differentials.)
The parameter number in parentheses is the one for use with the parameter unit (FR-PU07).
Parameter
Number
Name
Initial
Value
Setting
Range
Description