98
Setting of acceleration/deceleration time and acceleration/ deceleration pattern
(2) Deceleration time setting
(Pr. 8, Pr. 20)
Use
Pr. 8
Deceleration time
to set the deceleration time required to reach 0r/min from
Pr. 20
Acceleration/deceleration reference
speed
.
Set the deceleration time according to the following formula.
(3) Set two kinds of acceleration/deceleration times (RT signal,
Pr. 44, Pr. 45
)
Pr. 44
and
Pr. 45
are valid when the RT signal is ON.
When "9999" is set to
Pr. 45
, the deceleration time becomes equal to the acceleration time
(Pr. 44)
.
For the RT signal, set "3" in any of
Pr. 178 to Pr. 182 (input terminal function selection)
to assign the function.
(4) Setting the acceleration/deceleration time in the low-speed range
(Pr. 791, Pr. 792)
If torque is required in a low-speed range (lower than 10% of the rated speed), set
Pr. 791 Acceleration time in low-speed
range
and
Pr. 792 Deceleration time in low-speed range
settings higher than the
Pr. 7 Acceleration time
and
Pr. 8 Deceleration
time
settings so that the mild acceleration/deceleration is performed in the low-speed range.
The setting value of
Pr. 785 PM control torque boost
is the maximum generatable torque in the low-speed range.
(
)
For the acceleration time, set the time takes to accelerate from a stop to
Pr. 20 Acceleration/deceleration reference speed
. For
the deceleration time, set the time takes to decelerate from
Pr. 20 Acceleration/deceleration reference speed
to a stop.
Deceleration
time setting
=
Pr. 20
Deceleration time from maximum operating speed to stop
Maximum operating speed
Example) How to find the setting value for
Pr. 8
when decreasing the rotation
speed from the maximum speed of 1800r/min in 10s with
Pr. 20
=
3000r/min (initial setting).
Pr. 8
=
3000r/min
10s
16.7s
1800r/min
NOTE
When the acceleration/deceleration pattern is S-pattern acceleration/deceleration A
(refer to page 100)
, the acceleration/
deceleration time is the time required to reach the rated motor speed.
Changing terminal assignment may affect the other functions. Set parameters after confirming the function of each
terminal.
REMARKS
The RT signal acts as the second function selection signal and makes the other second function valid.
(Refer to page
120.)
If the
Pr. 20
setting is changed, the
Pr. 125
and
Pr. 126 (speed setting signal gain speed)
settings do not change. Set
Pr. 125
and
Pr. 126
to adjust the gains.
Set
Pr. 791
higher than
Pr. 7
, and
Pr. 792
higher than
Pr. 8
. If set as
Pr. 791
<
Pr. 7
, the operation is performed as
Pr. 791
=
Pr. 7
. If set as
Pr. 792
<
Pr. 8
, the operation is performed as
Pr. 792
=
Pr. 8
.
If the acceleration/deceleration time is set, the actual motor acceleration/deceleration time cannot be made shorter than
the shortest acceleration/deceleration time determined by the mechanical system J (moment of inertia) and motor
torque.
Parameters referred to
Pr. 29 Acceleration/deceleration pattern selection
Pr. 125, Pr. 126 (speed setting gain speed)
Pr. 178 to Pr. 182 (input terminal function selection)
Low-speed range
(r/min)
Acceleration time
Slope set by
Pr. 7
Deceleration time
Slope set by
Pr. 8
Deceleration time
in low-speed range
Slope set by
Pr. 792
Acceleration time
in low-speed range
Slope set by
Pr. 791
Time
Rotation speed