198
Communication operation and setting
(7) Setting items and set data
After completion of parameter settings, set the instruction codes and data then start communication from the computer to
allow various types of operation control and monitoring.
Item
Read/
Write
Instruction
Code
Data Definition
Number of
Data Digits
(Format)
Operation mode
Read
H7B
H0000: Network operation mode
H0001: External operation mode, External JOG operation mode
H0002: PU operation mode, External/PU combined operation mode 1 and
2, PUJOG operation mode
4 digits
(B, E/D)
Write
HFB
H0000: Network operation mode
H0001: External operation mode
H0002: PU operation mode (
Pr. 79
= "6")
4 digits
(A, C/D)
Monitor
Rotation
speed
/output
frequency
Read
H6F
H0000 to HFFFF: Rotation speed in 1r/min increments
Output frequency increments 0.01Hz (when
Pr. 144
= 4, 6 (2, 8, 10))
Machine speed increments 0.001 (when
Pr. 37
When "100" is set in
Pr. 52
, the monitor value is different depending on
whether the drive unit is at a stop or running.
4 digits
(B, E/D),
6 digits
(B, E2/D)
Output
current
Read
H70
H0000 to HFFFF: Output current (hexadecimal) in 0.01A increments
4 digits
(B, E/D)
Output
voltage
Read
H71
H0000 to HFFFF: Output voltage (hexadecimal) in 0.1V increments
4 digits
(B, E/D)
Special
monitor
Read
H72
H0000 to HFFFF: Monitor data selected in instruction code HF3
4 digits
(B, E/D),
6 digits
(B, E2/D)
Special
monitor
Selection No.
Read
H73
H01 to H50: Monitor selection data
Refer to the special monitor No. table on
page 200.
2 digits
(B, E1/D)
Write
HF3
2 digits
(A1, C/D)
Fault records
Read
H74 to H77
H0000 to HFFFF: Two latest fault records
Refer to the alarm data table on
page 201.
4 digits
(B, E/D)
Run command
(extended)
Write
HF9
Control input commands such as forward rotation (STF) signal and reverse
rotation (STR) signal. (For details,
refer to page 201
4 digits
(A, C/D)
Run command
Write
HFA
2 digits
(A1, C/D)
Drive unit status
monitor (extended)
Read
H79
Monitor the states of the output signals such as forward rotation, reverse
rotation and Drive unit running (RUN). (For details,
refer to page 202
4 digits
(B, E/D)
Drive unit status
monitor
Read
H7A
2 digits
(B, E1/D)
Set speed (RAM)
Read
H6D
Read the set speed/frequency from the RAM or EEPROM.
H0000 to HFFFF: speed setting increments 1r/min.
Setting frequency increments 0.01Hz (when
Pr. 144
= 4, 6 (2, 8, 10))
Machine speed increments 0.001 (when
Pr. 37
4 digits
(B, E/D),
6 digits
(B, E2/D)
Set speed
(EEPROM)
H6E
Set speed (RAM)
Write
HED
Write the set speed/frequency into the RAM or EEPROM.
H0000 to HFFFF: speed setting increments 1r/min.
Setting frequency increments 0.01Hz (when
Pr. 144
= 4, 6 (2, 8, 10))
Machine speed increments 0.001 (when
Pr. 37
To change the set speed/frequency consecutively, write data to the drive
unit RAM. (Instruction code: HED)
4 digits
(A, C/D),
6 digits
(A2, C/D)
Set speed
(RAM, EEPROM)
HEE
for data format (A, A1, A2, A3, B, C, C1, D, E, E1, E2, E3.)
The increment is 0.001 and the data format is E2 or A2 when the following conditions are met:
Pr. 37
= "0.01 to 9998,"
Pr. 144
= "2 to 10," and the
instruction code HFF = "01."
b15
b8b7
b0
Latest fault
First fault in past
Second fault in past
Third fault in past
Fourth fault in past
Fifth fault in past
Sixth fault in past
Seventh fault in past
H74
H75
H76
H77