179
Selection of operation mode and operation location
(4) Selection of control source in Network operation mode
(Pr. 338, Pr. 339)
There are two control sources: operation command source, which controls the signals related to the drive unit start
command and function selection, and speed command source, which controls signals related to speed setting.
In Network operation mode, the commands from the external terminals and communication are as listed below.
[Explanation of table]
External
: Command is valid only from control terminal.
NET
: Command only from communication is valid.
Combined : Command from both control terminal and communication is valid.
—
: Command from either of control terminal and communication is invalid.
Operation
Location
Selection
Pr. 338 Communication operation
command source
0: NET
1: External
Remarks
Pr. 339 Communication speed
command source
0: NET
1: External 2: External 0: NET
1: External 2: External
Fixed
function
(terminal-
equivalent
function)
Running speed from
communication
NET
—
NET
NET
—
NET
Terminal 2
—
External
—
—
External
—
Terminal 4
—
External
—
External
Se
le
ct
ive
f
u
nct
ion
Pr
. 178 to
Pr
. 1
82
setti
ng
0
RL
Low-speed operation
command/remote setting
clear
NET
External
NET
External
Pr. 59
=
"0"
(multi-speed)
Pr. 59
"0"
(remote)
1
RM
Middle-speed operation
command/remote setting
function
NET
External
NET
External
2
RH
High-speed operation
command/remote setting
function
NET
External
NET
External
3
RT Second function selection
NET
External
4
AU Terminal 4 input selection
—
Combined
—
Combined
5
JOG Jog operation selection
—
External
7
OH External thermal relay input
External
8
REX 15-speed selection
NET
External
NET
External
Pr. 59 =
"0"
(multi-speed)
10
X10 Drive unit run enable signal
External
12
X12
PU operation external
interlock
External
14
X14 PID control valid terminal
NET
External
NET
External
16
X16
PU/External operation
switchover
External
23
LX Pre-excitation
NET
External
24 MRS
Output stop
Combined
External
Pr. 79
"7"
PU operation interlock
External
Pr. 79 =
"7"
When the X12
signal is not
assigned
25 STOP Start self-holding selection
—
External
60 STF Forward rotation command
NET
External
61 STR Reverse rotation command
NET
External
62 RES Drive unit reset
External
64
X64
PID forward/reverse action
switchover
NET
External
NET
External
65
X65
PU/NET operation
switchover
External
66
X66
External/NET operation
switchover
External
67
X67
Command source
switchover
External
72
X72 PID integral value reset
NET
External
NET
External
REMARKS
The command source of communication is as set in
Pr. 551
.
The
Pr. 338
and
Pr. 339
settings can be changed while the drive unit is running when
Pr. 77
= "2". Note that the setting change is
reflected after the drive unit has stopped. Until the drive unit has stopped, communication operation command source and
communication speed command source before the setting change are valid.