Communication operation and setting
(6) MODBUS registers
The following shows the MODBUS registers for system environment variables (read/write), real time monitor items (read),
parameters (read/write), fault history data (read/write), and model information monitor items (read).
System environment variable
The communication parameter values are not cleared.
For write, set the data as a control input instruction.
For read, data is read as an drive unit operating status.
For write, set data as the operation mode setting.
For read, data is read as the operation mode status.
Register
Definition
Read/write
Remarks
40002
Drive unit reset
Write
Any value can be written
40003
Parameter clear
Write
Set H965A as a written value.
40004
All parameter clear
Write
Set H99AA as a written value.
40006
Parameter clear
Write
Set H5A96 as a written value.
40007
All parameter clear
Write
Set HAA99 as a written value.
40009
Drive unit status/control input instruction
Read/write
See below.
40010
Operation mode/drive unit setting
Read/write
See below.
40014
Running speed (RAM value)
Read/write
According to the
Pr. 37
and
Pr. 144
settings,
the selectable speed and frequency are in
0.01Hz increments.
40015
Running speed (EEPROM value)
Write
<
Drive unit status/control input instruction
>
The signal is the initial setting. Definitions change according to the
Pr. 180 to Pr. 182 (input terminal function selection) (refer to page 117)
.
Each assigned signal is valid or invalid depending on NET.
The signal is the initial setting. Definitions change according to the
Pr. 190, Pr. 192 (output terminal function selection) (refer to page123)
.
Writing is available depending on the
Pr. 79
and
Pr. 340
setting.
for details.
Bit
Definition
Control input instruction
Drive unit status
0
Stop command (Fixed)
RUN (drive unit running
(Variable))
1
Forward rotation command
(Fixed)
During forward rotation (Fixed)
2
Reverse rotation command
(Fixed)
During reverse rotation (Fixed)
3
RH (high-speed operation
command
(Variable))
Up-to-speed (Fixed)
4
RM (middle-speed operation
command
(Variable))
Overload (Fixed)
5
RL (low-speed operation
command
(Variable))
0
6
0
Speed detection (Fixed)
7
Second function selection (Fixed)
ABC (fault
(Variable))
8
Terminal 4 input selection (Fixed)
0
9
0
0
10
Output stop (Fixed)
0
11
0
0
12
0
0
13
0
0
14
0
0
15
0
Fault occurrence
<
Operation mode/drive unit setting
>
The restrictions depending on the operation
mode changes according to the computer
link specifications.
Mode
Read Value
Written
Value
EXT
H0000
PU
H0001
H0011
EXT
JOG
H0002
—
PU
JOG
H0003
—
NET
H0004
H0014
PU+EXT
H0005
—