171
Selection of operation mode and operation location
(11) Switching of operation mode by external signals (X65, X66 signals)
When
Pr. 79
= any of "0, 2, 6", the operation mode switching signals (X65, X66) can be used to change the PU or External
operation mode to the Network operation mode during a stop (during a motor stop or start command OFF). (
Pr. 79
= "6"
Switchover mode can be changed during operation)
When switching between the Network operation mode and PU operation mode
1)Set
Pr. 79
to "0" (initial value) or "6".
2)Set
"10" in
Pr. 340 Communication startup mode selection
.
3)Set "65" in any of
Pr. 178 to Pr. 182
to assign the PU/NET operation switchover (X65) signal to the terminal.
4)The operation mode changes to the PU operation mode when the X65 signal turns ON, or to the Network operation
mode when the X65 signal turns OFF.
When switching between the Network operation mode and External operation mode
1) Set
Pr. 79
to "0 (initial value), 2, 6 or 7". (At the
Pr. 79
setting of "7", the operation mode can be switched when the X12
(MRS) signal is ON.)
2) Set "0 (initial value) or 1" in
Pr. 340 Communication startup mode selection
.
3) Set "66" in any of
Pr. 178 to Pr. 182
to assign the External/NET operation switchover (X66) signal to the terminal.
4) The operation mode changes to the Network operation mode when the X66 signal turns ON, or to the External
operation mode when the X66 signal turns OFF.
Pr. 340
Setting
Pr. 79
Setting
X65 Signal State
Remarks
ON (PU)
OFF (NET)
10
0
(initial value)
PU operation mode
NET operation mode
—
1
PU operation mode
Fixed to PU operation mode
2
NET operation mode
Fixed to NET operation mode
3, 4
External/PU combined operation mode
External/PU combined mode fixed
6
PU operation mode
NET operation mode
Operation mode can be switched with operation continued
7
X12 (MRS)
ON
Switching among the External and PU
operation mode is enabled
Output stop in External operation mode
X12 (MRS)
OFF
External operation mode
Forcibly switched to External operation mode
NET operation mode when the X66 signal is ON.
PU operation mode when the X16 signal is OFF.
External operation mode when the X16 signal is ON.
Pr. 340
Setting
Pr. 79
Setting
X66 Signal State
Remarks
ON (NET)
OFF (external)
0
(initial
value)
, 1
0
(initial value)
NET operation mode
External operation
mode
—
1
PU operation mode
Fixed to PU operation mode
2
NET operation mode
External operation
mode
Cannot be switched to PU operation mode
3, 4
External/PU combined operation mode
External/PU combined mode fixed
6
NET operation mode
External operation
mode
Operation mode can be switched with
operation continued
7
X12 (MRS)
ON
NET operation mode
External operation
mode
Output stop in External operation mode
X12 (MRS)
OFF
External operation mode
Forcibly switched to External operation mode
PU operation mode when the X16 signal is OFF. When the X65 signal has been assigned, the operation mode changes with the ON/OFF state
of the X65 signal.
REMARKS
The priorities of
Pr. 79
,
Pr. 340
and signals are
Pr. 79
X12
X66
X65
X16
Pr. 340
.
NOTE
Changing the terminal assignment using
Pr. 178 to Pr. 182 (input terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 15 Jog speed setting
Pr. 4 to 6, Pr. 24 to 27, Pr. 232 to Pr. 239 Multi-speed operation
Pr. 75 Reset selection/disconnected PU detection/PU stop selection
Pr. 161 Speed setting/key lock operation selection
Pr. 178 to Pr. 182 (input terminal function selection)
Pr. 190, Pr. 192 (output terminal function selection)
Pr. 340 Communication startup mode selection
Содержание FR-D720-0.2K-G
Страница 45: ...34 MEMO ...
Страница 293: ...290 MEMO ...
Страница 294: ...291 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...