106
Selection and protection of a motor
The value left of the slash is for the 2.2K drive unit or lower. The one right of the slash is for the 3.7K drive unit.
The capacity of the S-PM geared motor is initially set to the next smaller size than the capacity of the drive unit.
The value left of the slash is for the 200V class drive unit. The one right of the slash is for the 400V class drive unit.
....... Specifications differ according to the date assembled.
to check the SERIAL number.
Before performing offline auto tuning
Check the following points before performing offline auto tuning:
A motor is connected. (Check that the motor is not rotated by an external force during tuning.)
The motor capacity is equal to or one rank lower than the drive unit capacity.
Using a motor with the rated current substantially lower than the drive unit rated current will cause torque ripples, etc. and
degrade the speed and torque accuracies. As a reference, select the motor with the rated motor current that is 40% or
higher of the drive unit rated current.
The wiring length between the drive unit and the motor should be 30m at maximum.
The motor may run slightly during offline auto tuning. (Tuning performance is unaffected.)
Therefore, fix the motor securely with a mechanical brake, or before tuning, make sure that there will be no problem in
safety if the motor runs. (Caution is required especially in vertical lift applications.)
Tuning may not be available for motors with an extremely low rated speed or motors for which magnetic saturation is
difficult to occur.
706
Induced voltage constant
(phi f)
9999
0 to 5000mV (s/rad)
Set the value according to the PM motor
specifications.
9999
The value calculated from the settings of the
motor constant parameters is used.
707
Motor inertia (integer)
9999
10 to 999
Set the motor inertia.
9999
Internal data of the drive unit is used.
711
Motor Ld decay ratio
9999
0 to 100%, 9999
Tuning data
(The value measured by offline auto tuning
is automatically set.)
9999: Internal data of the drive unit is used.
712
Motor Lq decay ratio
9999
0 to 100%, 9999
717
Starting resistance tuning
compensation
9999
0 to 200%, 9999
721
Starting magnetic pole
position detection pulse
width
9999
0 to 6000
μ
s, 9999
724
Motor inertia (exponent)
9999
4 to 7
Set the motor inertia.
9999
Internal data of the drive unit is used.
725
Motor protection current
level
9999
0 to 500%
Set the maximum current (OCT) level of the
motor.
9999
200%
726
Motor induced voltage
constant (phi f) exponent
9999
0 to 2
Set the exponent n when the induced
voltage constant phi f (
Pr. 706
) is multiplied
by 10^n.
9999
n = "0" when
Pr. 706
= "9999".
859
Rated PM motor current
9999
0 to 500A
Tuning data
(The value measured by offline auto tuning
is automatically set.)
9999
Internal data of the drive unit is used.
POINT
When the S-PM geared motor is used, offline auto tuning is not required.
Tuning is enabled even when a load is connected to the motor.
Reading/writing of the motor constants tuned by offline auto tuning is enabled. The offline auto tuning data
(motor constants) can be copied to another drive unit using a parameter unit.
The offline auto tuning status can be monitored on an operation panel or a parameter unit.
Parameter
Number
Name
Initial Value
Setting Range
Description
Содержание FR-D720-0.2K-G
Страница 45: ...34 MEMO ...
Страница 293: ...290 MEMO ...
Страница 294: ...291 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...