142
APPX
Appendix 2 Remote Registers
■
Operation condition setting completion flag (RWr0.b9)
To change the module settings during operation, write the setting data and then turn on the Operation condition setting
request flag (RWw0.b9). After the operation condition is changed, Operation condition setting completion flag (RWr0.b9) turns
on.
When the operation condition setting is requested, Warning code (RWr2) is set to 0000H and Warning status flag (RWr0.b12)
is turned off.
If the cause of the current error has been removed, Error code (RWr1) is set to 0000H, and Error status flag (RWr0.b10) is
turned off.
*1 When data link starts at the same time of when the module is powered on
*2 When an external input device connected to X0 is on
■
Error status flag (RWr0.b10)
Error status flag (RWr0.b10) turns on when a moderate error or major error occurs. Removing the cause of the error
(excluding a watchdog timer error) and turning on Error clear request flag (RWw0.b10) resets Error code (RWr1) to 0000H
and turns off the Error status flag (RWr0.b10).
If Error clear request flag (RWw0.b10) is turned on before removing the error cause, the error will be cleared but the Error
status flag (RWr0.b10) will be turned on again as long as the error cause remains.
When a major error has occurred, the error clear operation is not available.
Multiple errors occurring on multiple channels can be cleared collectively.
(1) The setting value is changed by a program.
(2) The operation starts with the default settings.
(3) The operation starts with the parameter setting value A.
ON
ON
(2)
(3)
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
(1)
500ms
Default
(Setting value A)
Module power supply
*1
Channel 1 (CQ) external input signal 0
(RX0)
*2
Controlled by the IO-Link module
Controlled by the program
Operation condition setting completion flag
(RWr0.b9)
Operation condition setting request flag
(RWw0.b9)
Remote READY (RWr0.b11)
Module setting
Содержание CC-Link IE Field NZ2GF12A-60IOLH8
Страница 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Страница 2: ......
Страница 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Страница 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Страница 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Страница 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Страница 157: ...I 155 MEMO ...
Страница 161: ......