56
6 Parameter Setting
6.3 Changing the IO-Link Module Parameters
Setting via a program
This section describes the procedure for changing the parameter.
Changing the network configuration
1.
Power on and off the module.
2.
Connect the modules again according to the desired network configuration.
3.
Power on the module.
4.
Perform the following steps 1 to 3.
Changing the parameters without changing the network configuration
1.
Use an RIWT instruction to set parameters to change.
For details on parameters and the procedure for setting parameters, refer to the following.
Page 83 Data that can be read and written in transient transmission
Page 101 Program Example of Setting Parameters Using a Dedicated Instruction
2.
Turn on Initial processing completion flag (RWw0.b8).
3.
Check that the Initial processing request flag (RWr0.b8) is turned off and there is no initial processing request. After the
check, turn off Initial processing completion flag (RWw0.b8).
4.
Check that Remote READY (RWr0.b11) is turned on.
Содержание CC-Link IE Field NZ2GF12A-60IOLH8
Страница 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Страница 2: ......
Страница 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Страница 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Страница 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Страница 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Страница 157: ...I 155 MEMO ...
Страница 161: ......