Swap function
This function swaps the upper and lower bytes of data sent and received between the IO-Link module and the IO-Link device
connected to each channel.
With this function, there is no need to program an operation to swap the upper and lower bytes when using an IO-Link device
that handles the upper and lower bytes in reverse.
Description
Enable or disable data swap for each channel using the parameter setting window of the engineering tool or via a program.
Enable this function by enabling the seventh bit of the corresponding channel of the process data size (access code: 20H) of
the data to be read or written in transient communication. (
To apply the data swap setting changed in processing other than the initial processing, turn on Operation condition setting
request flag (RWw0.b9).
For details on setting parameters via a program, refer to the following.
Setting procedure
1.
Open the "CC IE Field Configuration" window.
For the master/local module RJ71GF11-T2
[Navigation window]
[Parameter]
[Module Information]
[RJ71GF11-T2]
[Module Parameter]
[Basic Settings]
[Network Configuration Settings]
2.
Open the "Parameter Processing of Slave Station" window.
From the list of stations, select an IO-Link module
[CC IE Field Configuration]
[Online]
[Parameter Processing of
Slave Station].
3.
Set "Method selection" to "Parameter Write".
(1) IO-Link module
(2) IO-Link device
(3) Input area
(4) Output area
(5) Data swap
[H1] Data 1 upper byte
[L1] Data 1 lower byte
[H2] Data 2 upper byte
[L2] Data 2 lower byte
[H3] Data 3 upper byte
[L3] Data 3 lower byte
[H4] Data 4 upper byte
[L4] Data 4 lower byte
Unit: bytes
(1)
(3)
(4)
(5)
(2)
(3)
[L2]
[H1]
[L1]
[H2]
n+3
n
n+1
n+2
[L1]
[H1]
[L2]
[H2]
(4)
[L4]
[H3]
[L3]
[H4]
n+3
n
n+1
n+2
[L3]
[H3]
[L4]
[H4]
[H1]
[L1]
[H2]
[L2]
[H3]
[L3]
[H4]
[L4]
Содержание CC-Link IE Field NZ2GF12A-60IOLH8
Страница 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Страница 2: ......
Страница 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Страница 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Страница 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Страница 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Страница 157: ...I 155 MEMO ...
Страница 161: ......