84
7 FUNCTIONS
7.6 CC-Link IE Field Network Communication Function
■
IO-Link module identification data
Read IO-Link module identification data.
*1 Values are stored in alphanumeric ASCII code.
Ex.
The following table shows the identification data of the NZ2GF12A-60IOLH8 IO-Link module.
IO-Link module identification data is not writable. An error occurs in the RIWT instruction if the write is
attempted.
■
Initial operation setting
Enable/disable the initial processing when starting the IO-Link module.
• With initial processing: Initial processing request flag (RWr0.b8) is turned off and on at power-on and initial processing is
executed. When the initial processing is complete, the IO-Link module starts operation.
• Without initial processing: Initial processing is not executed at power-on, and the IO-Link module starts operation with the
default settings.
For details on the initial operation setting, refer to the following.
Page 140 Initial processing request flag (RWr0.b8)
Item
Description
Access code
10H
Attribute code
05H
Address code
10H
11H
12H
13H
14H
Data size
1 to 56 bytes
1 to 56 bytes
1 to 56 bytes
1 to 56 bytes
1 to 56 bytes
Data
Manufacturer name
Manufacturer text
Product name
Product ID
Product text
Address code
Stored value
Data size
10H
MITSUBISHI ELECTRIC CORPORATION
31 bytes
11H
http://www.MitsubishiElectric.co.jp/fa/
39 bytes
12H
NZ2GF12A-60IOLH8
16 bytes
13H
105
3 bytes
14H
IO-Link master module
21 bytes
Item
Description
Access code
11H
Attribute code
05H
Address code
00H
Data size
2 bytes
Data
• 0000H: With initial processing
• 0001H: Without initial processing
(Default: 0000H)
Содержание CC-Link IE Field NZ2GF12A-60IOLH8
Страница 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Страница 2: ......
Страница 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Страница 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Страница 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Страница 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Страница 157: ...I 155 MEMO ...
Страница 161: ......