7 FUNCTIONS
7.6 CC-Link IE Field Network Communication Function
93
7
Output HOLD/CLEAR setting function
This function sets the handling of the last output data when the IO-Link module is disconnected from data link or when the
CPU module is in the STOP state, RESET state, or ERROR STOP state. The operation of the IO-Link module varies
depending on whether the module is in the IO-Link mode or the SIO mode.
Output HOLD/CLEAR setting and its operation
When CLEAR or HOLD is set for an output, the output is turned on or off as follows.
■
When IO-Link mode is set
The operation of the IO-Link device of which output HOLD/CLEAR setting is set to CLEAR varies depending on the IO-Link
device connected. For details, refer to the manual of the IO-Link device.
The output HOLD/CLEAR setting function cannot be used on the IO-Link module of which firmware version is
"2.0". In this case, the IO-Link module operates based on the HOLD setting.
■
When SIO mode is set
• HOLD: Outputs the last output data.
• CLEAR: Outputs OFF.
To set HOLD or CLEAR to all output process data collectively, set the output HOLD/CLEAR setting of the data to be read or
written via transient communication.
*1 The output ON/OFF status is subject to the parameter settings (the output mode setting upon CPU error, output hold/clear setting upon
CPU STOP) of the master/local module.
The external input signal (RX) and external output signal (RY) will be turned off regardless of this setting if a
moderate or major error occurs on the IO-Link module.
Setting procedure
1.
Open the "CC IE Field Configuration" window.
For the master/local module RJ71GF11-T2
[Navigation window]
[Parameter]
[Module Information]
[RJ71GF11-T2]
[Module Parameter]
[Basic Settings]
[Network Configuration Settings]
Operating status
Output HOLD/CLEAR setting
CLEAR
HOLD
Data link in operation
CPU module in RUN
Data valid
Data valid
CPU module in STOP
Data invalid
Data valid
CPU module in PAUSE
Data valid
Data valid
CPU module in RESET
Data invalid
Data held
CPU module suspended by error
Data invalid
Data valid
During disconnection/cyclic stop
Data invalid
Data held
Operating status
HOLD/CLEAR setting
CLEAR (default)
HOLD/CLEAR setting
HOLD
Last output status
OFF
Last output status
ON
Last output status
OFF
Last output status
ON
Data link in
operation
CPU module in RUN
OFF
ON
OFF
ON
CPU module in STOP
OFF
ON/OFF
OFF
ON/OFF
CPU module in PAUSE
OFF
ON
OFF
ON
CPU module in RESET
OFF
OFF
OFF
ON
CPU module suspended by
error
OFF
ON/OFF
OFF
ON/OFF
During disconnection/cyclic stop
OFF
OFF
OFF
ON
Содержание CC-Link IE Field NZ2GF12A-60IOLH8
Страница 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Страница 2: ......
Страница 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Страница 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Страница 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Страница 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Страница 157: ...I 155 MEMO ...
Страница 161: ......