11 TROUBLESHOOTING
11.3 Checking the Status of IO-Link Devices
121
11
11.3
Checking the Status of IO-Link Devices
Check the status of the IO-Link device connected to each channel.
There are two methods for checking as follows.
• Using an engineering tool
• Using the RIRD instruction
Using an engineering tool
1.
Display the "Command Execution of Slave Station" window from the "CC IE Field Configuration" window.
From the list of stations, select an IO-Link module
[CC IE Field Configuration]
[Online]
[Command Execution of
Slave Station].
2.
Check the firmware version of the IO-Link module, and set "Method selection".
For the firmware version 2.0: "Device diagnostics for V2.0"
For the firmware version 2.0.2 or later: "Device diagnostics for V2.0.2 or later"
3.
Click the "Execute" button.
Using the RIRD instruction
Read event data of the IO-Link devices using the RIRD instruction.
For details, refer to the following.