Appendix 1 Remote I/O Signals
Channel n (CQ/Q) I/O switching command (RY10 to RY1F)
This command changes the mode of each channel to the SIO mode (digital output) or SIO mode (digital input). (n = 1 to 8)
Devices available for this signal differ depending on the mode.
Display LED1, LED2 (RY20, RY21)
Turn on or off these signals in combination to change the status of DISPLAY1 LED and DISPLAY2 LED.
: Available,
: Not available
Device
number
Signal name
Description
Mode
IO-
Link
mode
SIO mode
(digital
input)
SIO mode
(digital
output)
RY10
Channel 1 (CQ) I/O
switching command
• ON: Sets the CQ terminal of channel 1 to the SIO mode (digital output).
• OFF: Sets the CQ terminal of channel 1 to the SIO mode (digital input).
RY11
Channel 1 (Q) I/O
switching command
• ON: Sets the Q terminal of channel 1 to the SIO mode (digital output).
• OFF: Sets the Q terminal of channel 1 to the SIO mode (digital input).
RY12
Channel 2 (CQ) I/O
switching command
• ON: Sets the CQ terminal of channel 2 to the SIO mode (digital output).
• OFF: Sets the CQ terminal of channel 2 to the SIO mode (digital input).
RY13
Channel 2 (Q) I/O
switching command
• ON: Sets the Q terminal of channel 2 to the SIO mode (digital output).
• OFF: Sets the Q terminal of channel 2 to the SIO mode (digital input).
RY14
Channel 3 (CQ) I/O
switching command
• ON: Sets the CQ terminal of channel 3 to the SIO mode (digital output).
• OFF: Sets the CQ terminal of channel 3 to the SIO mode (digital input).
RY15
Channel 3 (Q) I/O
switching command
• ON: Sets the Q terminal of channel 3 to the SIO mode (digital output).
• OFF: Sets the Q terminal of channel 3 to the SIO mode (digital input).
RY16
Channel 4 (CQ) I/O
switching command
• ON: Sets the CQ terminal of channel 4 to the SIO mode (digital output).
• OFF: Sets the CQ terminal of channel 4 to the SIO mode (digital input).
RY17
Channel 4 (Q) I/O
switching command
• ON: Sets the Q terminal of channel 4 to the SIO mode (digital output).
• OFF: Sets the Q terminal of channel 4 to the SIO mode (digital input).
RY18
Channel 5 (CQ) I/O
switching command
• ON: Sets the CQ terminal of channel 5 to the SIO mode (digital output).
• OFF: Sets the CQ terminal of channel 5 to the SIO mode (digital input).
RY19
Channel 5 (Q) I/O
switching command
• ON: Sets the Q terminal of channel 5 to the SIO mode (digital output).
• OFF: Sets the Q terminal of channel 5 to the SIO mode (digital input).
RY1A
Channel 6 (CQ) I/O
switching command
• ON: Sets the CQ terminal of channel 6 to the SIO mode (digital output).
• OFF: Sets the CQ terminal of channel 6 to the SIO mode (digital input).
RY1B
Channel 6 (Q) I/O
switching command
• ON: Sets the Q terminal of channel 6 to the SIO mode (digital output).
• OFF: Sets the Q terminal of channel 6 to the SIO mode (digital input).
RY1C
Channel 7 (CQ) I/O
switching command
• ON: Sets the CQ terminal of channel 7 to the SIO mode (digital output).
• OFF: Sets the CQ terminal of channel 7 to the SIO mode (digital input).
RY1D
Channel 7 (Q) I/O
switching command
• ON: Sets the Q terminal of channel 7 to the SIO mode (digital output).
• OFF: Sets the Q terminal of channel 7 to the SIO mode (digital input).
RY1E
Channel 8 (CQ) I/O
switching command
• ON: Sets the CQ terminal of channel 8 to the SIO mode (digital output).
• OFF: Sets the CQ terminal of channel 8 to the SIO mode (digital input).
RY1F
Channel 8 (Q) I/O
switching command
• ON: Sets the Q terminal of channel 8 to the SIO mode (digital output).
• OFF: Sets the Q terminal of channel 8 to the SIO mode (digital input).
Display LED1, LED2 (RY20)
Display LED1, LED2 (RY21)
Status
ON
OFF
DISPLAY1 LED and DISPLAY2 LED are on in red.
OFF
ON
DISPLAY1 LED and DISPLAY2 LED are on in green.
ON
ON
DISPLAY1 LED and DISPLAY2 LED are on in orange.
OFF
OFF
DISPLAY1 LED and DISPLAY2 LED are off.
Содержание CC-Link IE Field NZ2GF12A-60IOLH8
Страница 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Страница 2: ......
Страница 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Страница 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Страница 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Страница 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Страница 157: ...I 155 MEMO ...
Страница 161: ......