11 TROUBLESHOOTING
11.6 List of Error Codes and the Warning Codes
127
11
D0A3H
Moderate error
The send processing of transient transmission has not
been done successfully.
• If an error has been detected on the own station,
target station, or relay station, check and address the
error.
• Correct the target station number of the transient
data, and retry the operation.
• If a module with another network number is
accessed, confirm that "Routing Setting" of "CPU
Parameter" is configured correctly.
E211H
Moderate error
The ISDU index is not available.
Refer to the manual of the connected IO-Link device
and correct the ISDU index.
E212H
Moderate error
The ISDU subindex is not available.
Refer to the manual of the connected IO-Link device
and correct the ISDU subindex.
E220H
Moderate error
The service is temporarily unavailable.
Wait some time and try again.
E221H
Moderate error
E222H
Moderate error
E223H
Moderate error
• Access to the ISDU write command is denied.
• Access to the ISDU read command is denied.
• The index is read-only.
• The index is write-only.
E230H
Moderate error
The parameter value is out of range.
Refer to the manual of the connected IO-Link device
and correct the parameter value.
E231H
Moderate error
The parameter value exceeds the defined value.
E232H
Moderate error
The parameter value is below the defined value.
E233H
Moderate error
The length of the parameter is too long.
Refer to the manual of the connected IO-Link device
and correct the parameter length.
E234H
Moderate error
The length of the parameter is too short.
E235H
Moderate error
The function is not available.
Refer to the manual of the connected IO-Link device.
E236H
Moderate error
The function is temporarily unavailable.
Wait some time and try again.
E240H
Moderate error
An invalid parameter is set.
Refer to the manual of the connected IO-Link device
and set a valid parameter.
E241H
Moderate error
An incompatible parameter is set.
Refer to the manual of the connected IO-Link device
and set a compatible parameter.
Error code
(hexadecimal)
Classification
Error definition and cause
Action
Содержание CC-Link IE Field NZ2GF12A-60IOLH8
Страница 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Страница 2: ......
Страница 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Страница 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Страница 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Страница 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Страница 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Страница 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Страница 157: ...I 155 MEMO ...
Страница 161: ......