MI 3325 MultiServicerXD
91
Connection diagrams
Figure 6.32: Connections of 3-wire test lead
Measurement procedure
Enter the
Riso
function (installation).
Set test parameters / limits.
Disconnect tested installation from mains supply and discharge installation as required.
Connect test cable to the instrument.
Connect 3-wire test lead to object under test. (See
Start the measurement. A longer press on
key or a longer press on
option
on touch screen starts a continuous measurement.
Stop the measurement. Wait until object under test is fully discharged.
Save results (optional).