MI 3325 MultiServicerXD
108
Test limits
Ia(Ipsc)
Minimum fault current for selected fuse
Connection diagram
Figure 6.65: Connection of Plug test cable or 3-wire test lead
Measurement procedure
Enter the
Z loop
function.
Set test parameters / limits.
Connect test cable to the instrument.
Connect 3-wire test lead or Plug test cable to the object under test, see
Start the measurement.
Save results (optional).
Figure 6.66: Examples of Loop impedance measurement result
6.2.17 Z loop m
– High precision fault loop impedance and
prospective fault current
Figure 6.67
: Z loop mΩ menu