MI 3325 MultiServicerXD
Appendix B
189
Figure B.5: Example of Trip-out time measurement result with enabled Random phase
Added new test parameter:
Test parameter
Random phase
[No, Yes]
Added tests with multiplication factor 2.
Modification of RCD Auto test procedure
RCD Auto test inserted steps
Notes
Re-activate RCD
.
Test with 2
I
N
, (+) positive polarity (new step 3).
RCD should trip-out
Re-activate RCD
.
Test with 2
I
N
, (-) negative polarity (new step 4).
RCD should trip-out
Inserted new Step 3
Inserted new Step 4
Figure B.6: Example of individual steps in RCD Auto test
– Inserted 2 new steps
Test results / sub-results
t I∆N x1 (+)
Step 1 trip-out time (I
=I
N
, (+) positive polarity)
t I∆N x1 (-)
Step 2 trip-out time (I
=I
N
, (-) negative polarity)
t I∆N x2 (+)
Step 3 trip-out time (I
=2
I
N
, (+) positive polarity)
t I∆N x2 (-)
Step 4 trip-out time (I
=2
I
N
, (-) negative polarity)
t I∆N x5 (+)
Step 5 trip-out time (I
=5
I
N
, (+) positive polarity)
t I∆N x5 (-)
Step 6 trip-out time (I
=5
I
N
, (-) negative polarity)
t I∆N x0.5 (+)
Step 7 trip-out time (I
=½
I
N
, (+) positive polarity)