MI 3325 MultiServicerXD
112
Fuse t
1)
Maximum breaking time of selected fuse
Isc factor
Correction factor Isc [0.2
… 3.0]
Test
3)
Selection of test [-, L-PE, L1-PE, L2-PE, L3-PE]
I ∆N
2)
Rated RCD residual current sensitivity [10 mA, 15 mA, 30 mA, 100 mA, 300
mA, 500 mA, 1000 mA]
RCD type
2)
RCD type [AC, A, F, B, B+]
Selectivity
2)
Characteristic [G, S]
I test
Test current [Standard, Low]
1)
Parameter or limit is considered if Protection is set to TN.
2)
Parameter or limit is considered if Protection is set to TTrcd.
3)
With Plug test cable or 3-wire test lead Zs rcd is measured in the same way regardless
of the setting. The parameter is meant for documentation.
Refer to
Fuse tables guide
for detailed information on fuse data.
Test limits
Ia(Ipsc)
1)
Minimum fault current for selected fuse
Limit Uc
Contact voltage limit [12 V, 25 V, 50 V]
1)
Parameter or limit is considered if Protection is set to TN.
Connection diagram
Figure 6.72: Connection of Plug test cable or 3-wire test lead
Measurement procedure
Enter the
Zs rcd
function.
Set test parameters / limits.
Connect test cable to the instrument.
Connect 3-wire test lead or Plug test cable to the object under test, see
Start the measurement.
Save results (optional).
Figure 6.73: Examples of Zs rcd measurement results