![METREL MultiServicerXD MI 3325 Скачать руководство пользователя страница 181](http://html1.mh-extra.com/html/metrel/multiservicerxd-mi-3325/multiservicerxd-mi-3325_instruction-manual_1779043181.webp)
MI 3325 MultiServicerXD
180
Input resistance ............................................... 20 M
Test terminals:
All results
TP1
11.31
Rpe – PE conductor resistance
RCD: No
R
– PE conductor resistance
Range
Resolution
Accuracy
Rpe
0.00
... 19.99
0.01
(5 % of r 5 digits)
20.0
... 99.9
0.1
100.0
... 199.9
0.1
10 % of reading
200
... 1999
1
Measuring current ............................................ min. 200 mA into PE resistance of 2
RCD:
Yes
, no trip out of RCD
R
– PE conductor resistance
Range
Resolution
Accuracy
Rpe
0.00
... 19.99
0.01
(5 % of r 10 digits)
20.0
... 99.9
0.1
100.0
... 199.9
0.1
10 % of reading
200
... 1999
1
Accuracy may be impaired in case of heavy noise on mains voltage.
Measuring current ............................................ < 15 mA
Nominal voltage range ..................................... 93 V
… 134 V (16 Hz … 400 Hz)
185 V
… 266 V (16 Hz … 400 Hz)
11.32
General data
Power supply
Supply voltage, frequency ............................... 110 V / 230 V AC, 50 Hz / 60 Hz
Supply voltage tolerance .................................
10 %
Max. power consumption ................................. 300 VA (without load on mains test socket)
Max. load ......................................................... 10 A continuous, 16 A short duration,
1.5 kW motor
Mains supply overvoltage category .................. CAT II / 300V
Altitude ............................................................
≤ 2000 m
Measuring categories
Mains test socket ............................................. CAT II / 300 V
IEC test socket ................................................ CAT II / 300 V
P/S terminal ..................................................... CAT II / 300 V
C1,C2,P1,P2 terminals .................................... CAT II / 300 V
Clamp inputs ................................................... CAT II / 300 V
Plug test cable ................................................. CAT II / 300 V
TP1 test socket ................................................ CAT III / 300 V
Protection classifications